Setting the Input Range and Alarm
Setup Example 2: Flow Rate Measurement Channel and Alarm
DX
Flowmeter
Channel 2
4 - 20 mA
Convert to 1-5 V with a shunt resistor
Setup Item
Description
Number in the Figure
Channel
Use channel 2.
1
Tag
FI-002
2
Input signal
1-5V
3
Input range
0.0 to 500.0 L/H
4
Alarm condition
Output an alarm if the measured value is
less than or equal to 120.0 L/H.
Output destination: Relay contact (I03)
5
(1) Input Range and Alarm
Press
MENU (switch to the setting mode).
Select the
Menu tab > Meas channel > Range, Alarm.
1
5
4
3
(2) Tag
Select the
Menu tab > Meas channel > Tag, Memory, Delay.
2
Operation complete.