4 configuration - ao block, 1 limits, Configuration - ao block -11 – Yokogawa YVP20S User Manual
Page 88: Limits -11
![background image](/manuals/360134/88/background.png)
9-11
IM 21B04C50-01E
<9. CONFIGURATION SERVICES>
9.4
Configuration - AO Block
This is the setup page related to the setpoint that is received from another function block or
a remote application. And I/O option contained in Analog Output (AO) Block.
Figure 9.5 Configuration - AO Block
9.4.1
Limits
● Setpoint High Limit (%)
Use this to limit the setpoint from another function block or remote application.
● Setpoint Low Limit (%)
Use this to limit the setpoint from another function block or remote application.
● Setpoint Rate High Limit (%/s)
The setpoint from another function block or remote application may also be limited to
change at a configurable ramp rate. The ramp rate up and the ramp rate down may be
individually configured. The default value is 1.#INF (infinity) which eliminates ramp rate
limiting.
● Setpoint Rate Low Limit (%/s)
See Set Point Up Rate Limit (%/s)
NOTE
The AO Block setpoint limits are different from the Position limits configured in the
Configure Position tab. The Position Limits apply to Target Position.