4 manual stop limits, Manual stop limits -3 – Yokogawa YVP20S User Manual
Page 101
10-3
IM 21B04C50-01E
<10. CALIBRATION SERVICES>
10.1.4 Manual Stop Limits
If Manual Stop Limits is selected, press GO button to execute a manual position calibration
process. The actuator moves to one stop and waits for user’s confirmation, and then moves
to the other stop for the other confirmation. The position at each stop will be measured and
saved. Wait until the valve has stopped moving before pressing the confirmation button.
Figure 10.4 Confirm Exhaust