beautypg.com

Yokogawa FVX110 User Manual

Page 72

background image

<11. Device Information>

11-2

IM 01S01C01-01EN

Table 11.2

Contents of DEVICE_STATUS_2 (index 1046)

Hexadecimal

Diplay through DD

Description

NAMUR

NE-107 category

0x80000000

LTB in O/S Mode

LCD Transducer Block is in O/S mode

C

0x40000000

LCD Failure

LCD has been failing

F

0x20000000

Amp Temp Out of Range

Amplifier temperature is out specification range

S

0x00008000

MAO1 in O/S Mode

MAO1 Block is in O/S mode

C

0x00004000

MAO1 in Man Mode

MAO1 Block is in Man mode

C

0x00002000

MAO1 Not Scheduled

MAO1 Block is not scheduled

C

0x00000800

MAO2 in O/S Mode

MAO2 Block is in O/S mode

C

0x00000400

MAO2 in Man Mode

MAO2 Block is in Man mode

C

0x00000200

MAO2 Not Scheduled

MAO2 Block is not scheduled

C

0x00000080

IS1 in O/S Mode

IS1 Block is in O/S mode

C

0x00000040

IS1 in Man Mode

IS1 Block is in Man mode

C

0x00000020

IS1 Not Scheduled

IS1 Block is not scheduled

C

0x00000008

IS2 in O/S Mode

IS2 Block is in O/S mode

C

0x00000004

IS2 in Man Mode

IS2 Block is in Man mode

C

0x00000002

IS2 Not Scheduled

IS2 Block is not scheduled

C

Table 11.3

Contents of DEVICE_STATUS_3 (index 1047)

Hexadecimal

Diplay through DD

Description

NAMUR

NE-107 category

0x80000000

PID1 in O/S Mode

PID1 Block is in O/S mode

C

0x40000000

PID1 in Man Mode

PID1 Block is in Man mode

C

0x20000000

PID1 Not Scheduled

PID1 Block is not scheduled

C

0x10000000

PID1 in Bypass Mode

PID1 Block is in Bypass mode

C

0x08000000

PID2 in O/S Mode

PID2 Block is in O/S mode

C

0x04000000

PID2 in Man Mode

PID2 Block is in Man mode

C

0x02000000

PID2 Not Scheduled

PID2 Block is not scheduled

C

0x01000000

PID2 in Bypass Mode

PID2 Block is in Bypass mode

C

0x00080000

SC in O/S Mode

SC Block is in O/S mode

C

0x00040000

SC in Man Mode

SC Block is in Man mode

C

0x00020000

SC Not Scheduled

SC Block is not scheduled

C

0x00008000

IT in O/S Mode

IT Block is in O/S mode

C

0x00004000

IT in Man Mode

IT Block is in Man mode

C

0x00002000

IT Not Scheduled

IT Block is not scheduled

C

0x00001000

IT Total Backup Err

IT Total Backup has failed. Last IT Output.Value(IT.LAST.

VALUE) is not saved

F

0x00000800

IT Conf. Err

IT Clock Period(IT.CLOCK_PER) is smaller than IT

Period of Execution(EXECUTION_PERIOD)

C

0x00000080

AR1 in O/S Mode

AR1 Block is in O/S mode

C

0x00000040

AR1 in Man Mode

AR1 Block is in Man mode

C

0x00000020

AR1 Not Scheduled

AR1 Block is not scheduled

C

0x00000010

AR1 Range Conf. Err

AR1 Range High(AR1.RANGE_HI) is smaller than AR1

Range Lo(AR1.RANGE_LO)

C

0x00000008

AR2 in O/S Mode

AR2 Block is in O/S mode

C

0x00000004

AR2 in Man Mode

AR2 Block is in Man mode

C

0x00000002

AR2 Not Scheduled

AR2 Block is not scheduled

C

0x00000001

AR2 Range Conf. Err

AR2 Range High(AR2.RANGE_HI) is smaller than AR2

Range Lo(AR2.RANGE_LO)

C