Index Index
PID1
Index
PID2
Parameter
Name
Default
(factory setting)
Write
Valid Range
Description
45
8045
8145 ALARM_SUM
Enable
The current alert status,
unacknowledged states, unreported
states, and disabled states of the
alarms associated with the function
block.
46
8046
8146 ACK_OPTION
0xFFFF
Selection of whether alarms associated
with the block will be automatically
acknowledged.
47
8047
8147 ALARM_HYS
0.5%
0 to 50%
Hysteresis for alarm detection and
resetting to prevent each alarm from
occurring and recovering repeatedly
within a short time.
48
8048
8148 HI_HI_PRI
0
0 to 15
Priority order of HI_HI_ALM alarm.
49
8049
8149 HI_HI_LIM
+INF
PV_SCALE
Setting for HI_HI_ALM alarm.
50
8050
8150 HI_PRI
0
0 to 15
Priority order of HI_ALM alarm.
51
8051
8151 HI_LIM
+INF
PV_SCALE
Setting for HI_ALM alarm.
52
8052
8152 LO_PRI
0
0 to 15
Priority order of LO_ALM alarm.
53
8053
8153 LO_LIM
-INF
PV_SCALE
Setting for LO_ALM alarm.
54
8054
8154 LO_LO_PRI
0
0 to 15
Priority order of LO_LO_ALM alarm.
55
8055
8155 LO_LO_LIM
-INF
PV_SCALE
Setting for LO_LO_ALM alarm.
56
8056
8156 DV_HI_PRI
0
0 to 15
Priority order of DV_HI_ALM alarm.
57
8057
8157 DV_HI_LIM
+INF
Setting for DV_HI_ALM alarm.
58
8058
8158 DV_LO_PRI
0
0 to 15
Priority order of DV_LO_ALM alarm.
59
8059
8159 DV_LO_LIM
-INF
Setting for DV_LO_ALM alarm.
60
8060
8160 HI_HI_ALM
—
—
Alarm that is generated when the PV
value has exceeded the HI_HI_LIM
value and whose priority order* is
defined in HI_HI_PRI.
* Priority order: Only one alarm is
generated at a time.
When two or more alarms occur at
the same time, the alarm having the
highest priority order is generated.
When the PV value has decreased
below [HI_HI_LIM - ALM_HYS],
HI_HI_ALM is reset.
61
8061
8161 HI_ALM
—
—
As above
62
8062
8162 LO_ALM
—
—
As above
Reset when the PV value has
increased above
[LO_LIM + ALM_HYS].
63
8063
8163 LO_LO_ALM
—
—
As above
64
8064
8164 DV_HI_ALM
—
—
Alarm that is generated when the
value of [PV - SP] has exceeded the
DV_HI_LIM value. Other features are
the same as HI_HI_ALM.
65
8065
8165 DV_LO_ALM
—
—
Alarm that is generated when the value
of [PV - SP] has decreased below the
DV_LO_LIM value. Other features are
the same as LO_LO_ALM.