7 bus power on, Bus power on -5 – Yokogawa FVX110 User Manual
Page 32

<5. Installation>
5-5
IM 01S01C01-01EN
Not used
0x00
0xF7
0xF8
0x0F
0x10
0x13
0x14
0xFB
0xFC
0xFF
V(FUN)
V(FUN)+V(NUN)
LM device
Bridge device
Unused
V(NUN)
BASIC device
Default address
Portable device address
F0508.ai
Note 1: Bridge device: A linking device which brings data
from one or more H1 networks.
Note 2: LM device: with bus control function (Link Master
function).
Note 3: BASIC device: without bus control function.
Figure 5.8
Available Address Range
5.7 Bus Power ON
Turn on the power of the host and the bus. After
displaying the startup screen shown in Figure 5.9,
the regular screen display appears. If the indicator
is not lit, check the polarity of the power supply.
F0509.ai
Figure 5.9
Using the host device display function, check that
the FVX110 is in operation on the bus.
The device information, including PD tag, Node
address, and Device ID, is described on the sheet
attached to the FVX110. The device information is
given in duplicate on this sheet.
DEVICE INFORMATION
Device ID
:
5945430010XXXXXXXX
PD Tag
:
UT1001
Device Revision
:
3
Node Address
:
0xf3
Serial No.
:
XXXXXXXXXXXXXXXXX
Physical Location :
Note:
Our Device Description Files and Capabilities Files available at
http://www.yokogawa.com/fld (English) or
http://www.yokogawa.co.jp/Sensor/fieldbus/fieldbus.htm (Japanese)
DEVICE INFORMATION
Device ID
:
5945430010XXXXXXXX
PD Tag
:
UT1001
Device Revision
:
3
Node Address
:
0xf3
Serial No.
:
XXXXXXXXXXXXXXXXX
Physical Location :
Note:
Our Device Description Files and Capabilities Files available at
http://www.yokogawa.com/fld (English) or
http://www.yokogawa.co.jp/Sensor/fieldbus/fieldbus.htm (Japanese)
F0510.ai
Figure 5.10 Device Information Sheet Attached to
FVX110
If no FVX110 is detected, check the available
address range and the polarity of the power supply.
If the node address and PD tag are not specified
when ordering, default value is factory set. If two
or more FVX110s are connected at a time with
default value, only one FVX110 will be detected
from the host as FVX110 have the same initial
address. Separately connect each FVX110 and set
a different address for each.