2 lcd transducer block, Lcd transducer block -4 – Yokogawa FVX110 User Manual
Page 77

<12. Parameter Lists>
12-4
IM 01S01C01-01EN
Relative
Index Index
Parameter Name
Factory Default Write
Mode
Explanation
86
1086 FD_CHECK_PRI
0
AUTO
Indicates the FD_CHECK_ALM priority for an alarm.
87
1087 FD_SIMULATE
AUTO
A parameter for simulating an alarm.
88
1088 FD_RECOMMEN_ACT
0
—
Indicates procedures for handling essential alarms.
89
1089 FD_EXTENDED_ACTIVE_1 0
—
A parameter serving as a starting point for alarms handled by
FF-912.
90
1090 FD_EXTENDED_ACTIVE_2 0
—
A parameter serving as a starting point for alarms handled by
FF-912.
91
1091 FD_EXTENDED_ACTIVE_3 0
—
A parameter serving as a starting point for alarms handled by
FF-912.
92
1092 FD_EXTENDED_ACTIVE_4 0
—
Not used by the FVX110.
93
1093 FD_EXTENDED_ACTIVE_5 0
—
Not used by the FVX110.
94
1094 FD_EXTENDED_ACTIVE_6 0
—
Not used by the FVX110.
95
1095 FD_EXTENDED_ACTIVE_7 0
—
Not used by the FVX110.
96
1096 FD_EXTENDED_ACTIVE_8 0
—
Not used by the FVX110.
97
1097 FD_EXTENDED_MAP_1 0x0748FFFF
AUTO
A parameter set by the user as a mask from DEVICE_
STATUS_1 to FD_EXTENDED_ACTIVE_1.
98
1098 FD_EXTENDED_MAP_2 0xE000EEEE
AUTO
A parameter set by the user as a mask from DEVICE_
STATUS_2 to FD_EXTENDED_ACTIVE_2.
99
1099 FD_EXTENDED_MAP_3 0xFF0EF8FF
AUTO
A parameter set by the user as a mask from DEVICE_
STATUS_3 to FD_EXTENDED_ACTIVE_3.
100
1100 FD_EXTENDED_MAP_4
AUTO
Not used by the FVX110.
101
1101 FD_EXTENDED_MAP_5
AUTO
Not used by the FVX110.
102
1102 FD_EXTENDED_MAP_6
AUTO
Not used by the FVX110.
103
1103 FD_EXTENDED_MAP_7
AUTO
Not used by the FVX110.
104
1104 FD_EXTENDED_MAP_8
AUTO
Not used by the FVX110.
105
1105 PRIVATE_1
—
Not used by the FVX110.
106
1106 PRIVATE_2
—
Not used by the FVX110.
107
1107 PRIVATE_3
—
Not used by the FVX110.
108
1108 PRIVATE_4
—
Not used by the FVX110.
109
1109 PRIVATE_5
—
Not used by the FVX110.
110
1110 PRIVATE_6
—
Not used by the FVX110.
111
1111 PRIVATE_7
—
Not used by the FVX110.
112
1112 PRIVATE_8
—
Not used by the FVX110.
113
1113 PRIVATE_9
—
Not used by the FVX110.
114
1114 PRIVATE_10
—
Not used by the FVX110.
115
1115 PRIVATE_11
—
Not used by the FVX110.
12.2 LCD Transducer Block
Relative
Index Index
Parameter Name
Factory Default Write
Mode
Explanation
0
2000 Block Header
TAG : "LTB"
"Block
Tag
=O/S"
Information on this block such as Block Tag, DD Revision,
Execution Time, etc.
1
2001 ST_REV
-
AUTO
Describes the revision level of parameters for setting the
transducer block. The revision is updated when set values
are changed. This parameter is used to check for parameter
changes.
2
2002 TAG_DESC
Null
AUTO
A universal parameter intended for storing comments describ-
ing tag data.
3
2003 STRATEGY
1
AUTO
A universal parameter used by the high-level system to iden-
tify function blocks.
4
2004 ALERT_KEY
1
AUTO
Key information used to identify the location at which an alert
occurred. Generally, this parameter is used by a high-level
system to identify specific areas in a plant that are under the
control of specific operators to distinguish necessary alarms
only. This is a universal parameter.