beautypg.com

4 setting of tags and addresses, 5 communication setting, 1 vcr setting – Yokogawa FVX110 User Manual

Page 37: Setting of tags and addresses -4, Communication setting -4 6.5.1, Vcr setting -4

background image

<6. Configuration>

6-4

IM 01S01C01-01EN

6.4 Setting of Tags and

Addresses

This section describes the steps in the procedure

to set PD Tags and node addresses in the FVX110.

There are three states of Fieldbus devices as

shown in Figure 6.4, and if the state is other than

the lowest SM_OPERATIONAL state, no function

block is executed. FVX110 must be transferred

to this state when an FVX110 tag or address is

changed.

UNINITIALIZED

(No tag nor address is set)

Tag clear

Tag setting

INITIALIZED

(Only tag is set)

SM_OPERATIONAL

(Tag and address are retained, and

the function block can be executed.)

Address clear

F0604.ai

Address setting

Figure 6.4

Status Transition by Setting PD Tag and

Node Address

FVX110 has a PD Tag (UT1001) and node

address (245, or hexadecimal F5) that are set

upon shipment from the factory unless otherwise

specified. To change only the node address, clear

the address once and then set a new node address.

To set the PD Tag, first clear the node address and

clear the PD Tag, then set the PD Tag and node

address again.
Devices whose node addresses have been cleared

will have the default address (randomly chosen

from a range of 248 to 251, or from hexadecimal

F8 to FB). At the same time, it is necessary to

specify the device ID in order to correctly specify

the device. The device ID of the FVX110 is

5945430010xxxxxxxx. (The xxxxxxxx at the end

of the above device ID is a total of 8 alphanumeric

characters.)

6.5 Communication Setting

To set the communication function, it is necessary

to change the database residing in SM-VFD.

6.5.1 VCR Setting

Set VCR (Virtual Communication Relationship),

which specifies the called party for communication

and resources. FVX110 has 35 VCRs whose

application can be changed, except for the first

VCR, which is used for management.
FVX110 has VCRs of four types:
Server(QUB) VCR

A Server responds to requests from a host. This

communication needs data exchange. This

type of communication is called QUB (Queued

User-triggered Bidirectional) VCR.

Source (QUU) VCR

A Source multicasts alarms or trends to other

devices. This type of communication is called

QUU (Queued User-triggered Unidirectional)

VCR.

Publisher (BNU) VCR

A Publisher multicasts AI block output of field

device to another function block(s). This type

of communication is called BNU (Buffered

Network-triggered Unidirectional) VCR.

Subscriber (BNU) VCR

A Subscriber receives output of another

function block(s) by MAO block or PID block.

A Server VCR is capable to responding to

requests from a Client (QUB) VCR after the Client

successfully initiates connection to the Server. A

Source VCR transmits data without established

connection. A Sink (QUU) VCR on another device

can receive it if the Sink is configured so. A

Publisher VCR transmits data when LAS requests

so. An explicit connection is established from

Subscriber (BNU) VCR(s) so that a Subscriber

knows the format of published data.
Each VCR has the parameters listed in Table 6.4.

Parameters must be changed together for each

VCR because modification of individual parameters

may cause inconsistent operation.