A4-8 – Yokogawa FVX110 User Manual
Page 131

A4-8
IM 01S01C01-01EN
Relative
Index
Index
AR1
Index
AR2
Parameter
Write
Mode
Valid
Range
Initial
Value
View
Description / Remarks
1 2 3 4
29
17529 17629 ARITH_
TYPE
1 to 10
0x01
1 Computation algorithm identification no.
Value Selection Name
Description
1
Flow
compensation,
linear
Flow compensation
(linear)
2
Flow
compensation,
square root
Flow compensation
(square root)
3
Flow
compensation,
approximate
Flow compensation
(approximate
expression)
4
BTU flow (*)
Quantity of heat
calculation
5
Traditional Multiply
Divide
Multiplication and
division
6
Average
Average calculation
7
Traditional summer Summation
8
Fourth order
Polynomial, Type 1
4th-order (auxiliary
input) polynomial
computation
9
HTG level
compensation (*)
HTG-level
compensation
10
Fourth order
Polynomial, Type 2
4th-order (main
input) polynomial
computation
* BTU stands for British thermal unit.
HTG stands for hydrostatic tank gauging.
30
17530 17630 BAL_TIME
More
than 0
0
4 Time taken to return to the set value.
31
17531 17631 BIAS
0
4 Bias value used to calculate the output.
32
17532 17632 GAIN
1
4 Gain value used to calculate the output.
33
17533 17633 OUT_HI_
LIM
+INF
4 Maximum output value.
34
17534 17634 OUT_LO_
LIM
-INF
4 Minimum output value.
35
17535 17635 UPDATE_
EVT
Indicates event information if an update event
(setting change) occurs.
36
17536 17636 BLOCK_
ALM
Indicates alarm information if a block alarm occurs.