A3-1 – Yokogawa digitalYEWFLO (DY-FF) User Manual
Page 81
A3-1
IM 01F06F00-01EN
APPENDIX 3. OPERATION OF EACH
PARAMETER IN FAILURE MODE
*1: Standard Type and Multi-variable Type with THERMOMETER_FUNCTION in TR block Set to “Monitor Only” or “Not Use”
*2: Multi-variable Type with THERMOMETER_FUNCTION Used for Density Calculation
LCD
Display
Alarm Detail
RS Block
TR Block
AI1 Block
AI2 Block
AI3 Block
Alarm Reset
SW* (default)
AL-01
AMP. Module
Failure 1 (AL-01)
—
Other
• Default
Bad-Non Specifi c
• STATUS_OPTS:Propagate Fault Forward = Active
Bad-Device Failure
Not provided
AMP. Module
Failure 1 (AL-01)
Bad-Device
Failure
• Default
Bad-Non Specifi c
• STATUS_OPTS:Propagate Fault Forward = Active
Bad-Device Failure
Bad-Device
Failure
AL-02
COM. Circuit
Failure 1 (AL-02)
—
Other
• Default
Bad-Non Specifi c
• STATUS_OPTS:Propagate Fault Forward = Active
Bad-Device Failure
Not provided
COM. Circuit
Failure 1 (AL-02)
Bad-Device
Failure
• Default
Bad-Non Specifi c
• STATUS_OPTS:Propagate Fault Forward = Active
Bad-Device Failure
Bad-Device
Failure
AL-03
COM. Circuit
Failure 2 (AL-03)
—
Other
• Default
Bad-Non Specifi c
• STATUS_OPTS:Propagate Fault Forward = Active
Bad-Device Failure
Not provided
COM. Circuit
Failure 2 (AL-03)
Bad-Device
Failure
• Default
Bad-Non Specifi c
• STATUS_OPTS:Propagate Fault Forward = Active
Bad-Device Failure
Bad-Device
Failure
AL-04
AMP. Module
Failure 2 (AL-04)
Lost Static Data
Lost MV Data
Other
Bad-Non Specifi c
Not provided
AMP. Module
Failure 2 (AL-04)
Bad-Non Specifi c
Bad-Non Specifi c
Bad-Non Specifi c
AL-05
Flow Sensor
Failure (AL-05)
—
Other
Uncertain-Non
Specifi c
Uncertain-Non
Specifi c
Provided
(ON)
Flow Sensor
Failure (AL-05)
Uncertain-
Sensor
Conversion not
Accurate
Uncertain-Non
Specifi c
Uncertain-Non
Specifi c