6.2 Transducer Block Parameters
The transducer block sets functions specifi c to the
fl ow rate measurement of the digitalYEWFLO. For
each block parameter in digitalYEWFLO, refer
to APPENDIX 1 “LIST OF PARAMETERS FOR
EACH BLOCK OF digitalYEWFLO.” The following
describes important parameters and how to set
them.
For the METHOD of TR block, refer to APPENDIX
10.1 “Transducer Block”.
(1) Mandatory Parameter Setting for
Transducer Block
After setting parameters of the transducer block,
set up XD_SCALE of the AI1 block (and of the
AI2 block as appropriate).
Table 6.1 shows the parameters that must be
set (in order of the relative index sequentially)
depending on the operation conditions.
Table 6.1
Mandatory Parameter Setting for Transducer Block Depending on Operation Conditions
Relative Index
Parameter
Name
Operation Conditions
47
SENSOR_
STATUS
1 =
Standard
1 =
Standard
2 = Built-in
Temp.
Sensor
2 = Built-in
Temp.
Sensor
2 = Built-in
Temp.
Sensor
2 = Built-in
Temp.
Sensor
2 = Built-in
Temp.
Sensor
2 = Built-in
Temp.
Sensor
48
THERMOMETER_
FUNCTION
—
—
1 = Monitor
only; or
6 = Not use
1 = Monitor
only; or
6 = Not use
2 =
Saturated
steam
3 =
Superheat
steam
4 = GAS:
STD/Normal
5 = LIQUID:
Mass
49 FLUID_TYPE
1 = LIQUID:
Volume;
2 =
GAS/
STEAM:
Volume;
3 =
LIQUID:
Mass or
4 =
GAS/
STEAM:
Mass
5 = GAS:
STD/Normal
1 = LIQUID:
Volume;
2 =
GAS/
STEAM:
Volume;
3 =
LIQUID:
Mass or
4 =
GAS/
STEAM:
Mass
5 = GAS:
STD/Normal
—
—
—
—
Mandatory
50
TEMPERATURE_
UNIT
51 PROCESS_TEMP
52 BASE_TEMP
53 DENSITY_UNIT
54
PROCESS_
DENSITY
55 BASE_DENSITY
56
PRESSURE_
UNIT
57
PROCESS_
PRESSURE
58
BASE_
PRESSURE
59 DEVIATION
62
FIRST_TEMP_
COEF
63
SECOND_TEMP_
COEF