A2-5, The following units can be displayed on the lcd: m, Min, m – Yokogawa digitalYEWFLO (DY-FF) User Manual

Page 79: H, l/min, l/h, nm, Min, nm, H, kg/min, kg/h, t/min, and t/h

background image

A2-5

IM 01F06F00-01EN

The UPPER_DISPLAY_MODE and LOWER_
DISPLAY_MODE parameter settings in the
transducer (TR) block, and the L_TYPE settings in
the AI1 and AI2 blocks determine which data items,
and their values and units, are displayed on the
LCD indicator, as shown in the following tables.

Display on Upper Row of LCD Indicator

UPPER_DISPLAY_MODE

Displayed Value, Display Unit, and Display Format

FLOW RATE (%)

L_TYPE of AI1

= DIRECT

= INDIRECT

Value

Percentage calculated from OUT.
Value and XD_SCALE of AI1
(see note 1)

Percentage calculated from OUT.Value
and OUT_SCALE of AI1 (see note 2)

Unit %
Format

Number, to one decimal place

FLOW RATE

L_TYPE of AI1

= DIRECT

= INDIRECT

Value

OUT.Value of AI1

OUT.Value of AI1 (scaled based on
XD_SCALE and OUT_SCALE)

Unit As

specifi ed by XD_SCALE.Units

Index of AI1

As specifi ed by OUT_SCALE.Units
Index of AI1

Format

Determined by the value of
XD_SCALE.EU at 100 of AI1.

Determined by the value of
OUT_SCALE.EU at 100 of AI1.

TEMPERATURE (%)

L_TYPE of AI2

= DIRECT

= INDIRECT

Value

Percentage calculated from OUT.
Value and XD_SCALE of AI2
(see note 1)

Percentage calculated from OUT.Value
and OUT_SCALE of AI2 (see note 2)

Unit %
Format

Number, to one decimal place

Arithmetic Out

Value

AR OUT.Value

Unit

AR OUT_RANGE. Units Index

Format

AR OUT_RANGE. Eu_100, Eu_0

Note 1: If L_TYPE is set to DIRECT, the following equation applies to determine the displayed percentage:

Percentage = (OUT.Value – XD_SCALE.EU at 0) / (XD_SCALE.EU at 100 – XD_SCALE.EU at 0)

 100

Note 2: If L_TYPE is set to INDIRECT, the following equation applies to determine the displayed percentage:

Percentage = (OUT.Value – OUT_SCALE.EU at 0) / (OUT_SCALE.EU at 100 – OUT_SCALE.EU at 0)

 100

Display on Lower Row of LCD Indicator

UPPER_DISPLAY_MODE

Displayed Value, Display Unit, and Display Format

BLANK Value

Blank

Unit Blank

TOTAL Value

TOTAL_VAL

of

AI1

Unit

TERTIARY_VALUE_UNIT of transducer block (note 3)

Format

Determined by TOTAL_RATE_VAL of AI1.

TEMPERATURE

L_TYPE of AI2

= DIRECT

= INDIRECT

Value

OUT.Value of AI2 (scaled based on
XD_SCALE)

OUT.Value of AI2 (scaled based on
XD_SCALE and OUT_SCALE)

Unit

XD_SCALE.Units Index of AI2

OUT_SCALE.Units Index of AI2 (but
without indication of "%")

Format

Number, to one decimal place

Integrator Out

Value

IT OUT.Value

Unit

IT OUT_RANGE. Units Index

Format

IT OUT_RANGE. Eu_100, Eu_0

Note 3: The unit displayed for the totalized fl ow rate (TOTAL) is the value of TERTIARY_VALUE_UNIT in the transducer block, which is

determined by the value of XD_SCALE.Units Index in the AI1 block.

Note 4: AI3 block does not display because it is the function block for fl ow calculation in the AR block.

The following units can be displayed on the LCD: m

3

/min, m

3

/h, L/min, L/h, Nm

3

/min, Nm

3

/h, kg/min, kg/h, t/min,

and t/h.