A8-3 – Yokogawa digitalYEWFLO (DY-FF) User Manual
Page 129
A8-3
IM 01F06F00-01EN
Index Parameter Name
Default
(factory setting)
Write Valid
Range
Description
36 ROUT_OUT
0
–
Remote control output value
37 TRK_SCALE
100
0
1342 (%)
1
MAN
Upper and lower scale limits used to convert the output
tracking value (TRK_VAL) to non-dimensional.
38 TRK_IN_D
0
Switch for output tracking. Refer to APPENDIX 8.12
“External-output Tracking” for details.
39 TRK_VAL
0
Output tracking value (TRK_VAL)
When MODE_BLK.actual = LO, the value scaled from the
TRK_VAL value is set in OUT.
40 FF_VAL
0
Feedforward input value.
The FF_VAL value is scaled to a value with the same scale
as for OUT, multiplied by the FF_GAIN value, and then
added to the output of the PID computation.
41 FF_SCALE
100
0
1342 (%)
1
MAN
Scale limits used for converting the FF_VAL value to a non-
dimensional value.
42 FF_GAIN
0
MAN
Gain for FF_VAL
43 UPDATE_EVT
–
Same as that for an AI block.
44 BLOCK_ALM
–
Same as that for an AI block.
45 ALARM_SUM
Enable
Same as that for an AI block.
46 ACK_OPTION
0
Same as that for an AI block.
47 ALARM_HYS
0.5%
0 to 50%
Hysteresis for alarm detection and resetting to prevent each
alarm from occurring and recovering repeatedly within a
short time.
48 HI_HI_PRI
0
0 to 15
Priority order of HI_HI_ALM alarm
49 HI_HI_LIM
1.#INF
PV_SCALE
Setting for HI_HI_ALM alarm
50 HI_PRI
0
0 to 15
Priority order of HI_ALM alarm
51 HI_LIM
1.#INF
PV_SCALE
Setting for HI_ALM alarm
52 LO_PRI
0
0 to 15
Priority order of LO_ALM alarm
53 LO_LIM
-1.#INF
PV_SCALE
Setting for LO_ALM alarm
54 LO_LO_PRI
0
0 to 15
Priority order of LO_LO_ALM alarm
55 LO_LO_LIM
-1.#INF
PV_SCALE
Setting for LO_LO_ALM alarm
56 DV_HI_PRI
0
0 to 15
Priority order of DV_HI_ALM alarm
57 DV_HI_LIM
1.#INF
Setting for DV_HI_ALM alarm
58 DV_LO_PRI
0
0 to 15
Priority order of DV_LO_ALM alarm
59 DV_LO_LIM
-1.#INF
Setting for DV_LO_ALM alarm
60 HI_HI_ALM
–
–
Alarm that is generated when the PV value has exceeded
the HI_HI_LIM value and whose priority order* is defi ned in
HI_HI_PRI.
* Priority order: Only one alarm is generated at a time.
When two or more alarms occur at the same time, the alarm
having the highest priority order is generated. When the
PV value has decreased below [HI_HI_LIM – ALM_HYS],
HI_HI_ALM is reset.
61 HI_ALM
–
–
As
above
62 LO_ALM
–
–
As
above
Reset when the PV value has increased above
[LO_LIM + ALM_HYS].
63 LO_LO_ALM
–
–
As
above
64 DV_HI_ALM
–
–
Alarm that is generated when the value of [PV - SP] has
exceeded the DV_HI_LIM value. Other features are the
same as HI_HI_ALM.
65 DV_LO_ALM
–
–
Alarm that is generated when the value of [PV - SP] has
decreased below the DV_LO_LIM value. Other features are
the same as LO_LO_ALM.