IM 01F06F00-01EN
A4-2. Make the parameters in the current LAS
match the capabilities parameter in the
digitalYEWFLO as follows (Refer to Section
5.2 “Network Defi nition”):
LAS
digitalYEWFLO
V(ST)
>
V(ST)
≥ 4
V(MID)
>
V(MID)
≥ 4
V(MRD)
>
V(MRD)
≥ 12
A4-3. Check that the digitalYEWFLO is assigned
an appropriate address. The address of
the digitalYEWFLO must not lie within
either 0x00 to 0x10 or the range of unused
(unpolled) node addresses determined by
the current LAS’s LM parameter settings,
which is V(FUN) to V(FUN) + V(NUM).
(Refer to Section 5.2 “Network Defi nition.”)