- 46 -
Setting requirement
A: Required (function selection)
B: Required (network environment, etc.)
C: Checked (As a rule, the default value
on the parameter list must be used.)
Modbus/
TCP
IAI protocol
B/TCP
Transmission by
SEL program
No. Parameter
name
Default
value
(reference)
Input range
Unit
Remarks
A
C C
8
Expanded I/O3
input-port start
number based on
fixed assignment
(I/O4)
-1 -1~599
0 + (Multiple of 8) (A negative value is invalid.)
-1: No expanded I/O3 DI
A
C C
9
Expanded I/O3
output-port start
number based on
fixed assignment
(I/O3)
-1 -1~599
300 + (Multiple of 8) (A negative value is invalid.)
-1: No expanded I/O3 DO
A
C C
10
Standard I/O error
monitor (I/O1)
1 0~5
0: Do not monitor
1: Monitor
2: Monitor (Do not monitor 24 V I/O power error)
3: Monitor (Monitor 24 V I/O power error only)
A
C C
11
Expanded I/O1
error monitor (I/O2)
1 0~5
A
C C
12
Expanded I/O2
error monitor (I/O3)
1 0~5
A
C C
13
Expanded I/O3
error monitor (I/O4)
1 0~5
A
14
Number of ports
using network
I/F-card remote
input
0 0~256
Specify the Modbus/TCP remote DI bits by a multiple of 8
(8
n 256).
A
15
Number of ports
using network
I/F-card remote
output
0 0~256
Specify the Modbus/TCP remote DO bits by a multiple of 8
(8
n 256).