E-Mon E-PS-A-RTU-N User Manual
Page 96

Chapter 4 Power
S O F T W A R E
E N 5 0 1 6 0 E V A L U A T I O N A N D
R E C O R D I N G
96
PowerSmart+ Advanced Power Quality Meter
Adjust limits you want to change.
Download your setup to the device.
The default EN50160 compliance limits are shown in the picture above. You can change
the number of the evaluated harmonics and interharmonics via the
EN50160 Advanced
Setup
.
EN50160 Advanced Setup
EN50160 Advanced Setup
EN50160 Advanced Setup
EN50160 Advanced Setup
The EN50160 Advanced Setup allows you to configure the EN50160 evaluation options in
your meter.
To configure the EN50160 evaluation options:
Select Memory/Log from the Meter Setup menu, and then click on the EN50160 Advanced
Setup tab.
Change the EN50160 evaluation options if required.
Download your setup to the device.
The default EN50160 evaluation options set in your device are shown in the picture below.
The available options are listed in the following table.
Option
Range
Default
Description
EN50160 Compliance Statistics
Evaluation
Disabled,
Enabled
Enabled
Enables the EN50160 evaluation
Evaluation
Period
Daily,
Weekly
Weekly
Defines the EN50160 statistics evaluation period
First Day of the
Week
Sunday-
Saturday
Sunday
Defines the first day of the week for statistics
evaluated on a weekly basis
EN50160 Harmonics Survey
Evaluation
Disabled,
Enabled
Enabled
Enables the harmonics survey log
Evaluation
Period
Daily,
Weekly
Weekly
Defines the harmonics survey evaluation period