Appendix A Technical Specifications
130
PowerSmart+ Advanced Power Quality Meter
Measurement Specifications
Accuracy
Parameter
Full Scale @ Input
Range
%
Reading
% FS
Conditions
Range
Voltage
120VxPT @ 120V
400VxPT @ 690V
0.2
0.01
10% to 120% FS
0 to 1,150,000 V
Starting voltage
1.5% FS @ 120V
1.5% FS @ 690V
Line current
CT
0.2
0.02
1% - 200% FS
0 to 40,000 A
Starting current 0.1% FS
Active power
0.36×PT×CT @ 120V
1.2×PT×CT @ 690V
0.2
0.02
|PF| ≥ 0.5
1
-10,000,000 kW to
+10,000,000 kW
Reactive power
0.36×PT×CT @ 120V
1.2×PT×CT @ 690V
0.3
0.04
|PF| ≤ 0.9
1
-10,000,000 kvar to
+10,000,000 kvar
Apparent power
0.36×PT×CT @ 120V
1.2×PT×CT @ 690V
0.2
0.02
|PF| ≥ 0.5
1
0 to 10,000,000 kVA
Power factor
1.000
0.2
|PF| ≥ 0.5,
I ≥ 2% FSI
-0.999 to +1.000
Frequency
0.02
40 Hz to 70 Hz
Total Harmonic
Distortion, THD
V (I), %Vf (%If)
999.9
1.5
0.1
THD ≥ 1%,
V (I) ≥ 10% FSV
(FSI)
0 to 999.9
Total Demand
Distortion, TDD,
%
100
1.5
TDD ≥ 1%,
I ≥ 10% FSI
0 to 100
Active energy
Import & Export
Class 0.2S under conditions as per IEC
62053-22:2003
0 to 999,999.999 MWh
Reactive energy
Import & Export
Class 0.2S under conditions as per IEC
62053-22:2003, |PF| ≤ 0.9
0 to 999,999.999 Mvarh
Apparent energy
Class 0.2S under conditions as per IEC
62053-22:2003
0 to 999,999.999 MVAh
1
@ 80% to 120% of voltage FS, 1% to 200% of current FS, and frequency 50/60 Hz
PT - external potential transformer ratio
CT - primary current rating of external current transformer
FSV - voltage full scale
FSI - current full scale
Vf - fundamental voltage
If - fundamental current
NOTES
1. Accuracy is expressed as ± (percentage of reading + percentage of full scale) ± 1 digit.
This does not include inaccuracies introduced by the user's potential and current
transformers. Accuracy calculated at 1second average.
2. Voltage and Current measurement accuracy is ≤ 0.05 % at nominal value
3. Specifications assume: voltage and current waveforms with THD ≤ 5% for kvar, kVA
and PF, and reference operating temperature 20°C - 26°C.
4. Measurement error is typically less than the maximum error indicated.