Chapter 2 Installation
Electrical Installation
PowerSmart+ Advanced Power Quality Meter
19
Wiring Configuration
(See Basic Device Settings in Chapter 3)
Setup Code
Figure
3-wire 2-element Direct connection using 2 CTs
3dir2
2-17
4-wire Wye 3-element direct connection using 3 CTs
4Ln3 or 4LL3
2-18
4-wire Wye 3-element connection using 3 PTs, 3 CTs
4Ln3 or 4LL3
2-19
3-wire 2-element Open Delta connection using 2 PTs, 2 CTs
3OP2
2-20
4-wire Wye 2½ -element connection using 2 PTs, 3 CTs
3Ln3 or 3LL3
2-21
3-wire 2½ -element Open Delta connection using 2 PTs, 3 CTs
3OP3
2-22
4-wire 3-element Delta direct connection using 3 CTs
4Ln3 or 4LL3
2-23
3-wire 2½-element Broken Delta connection using 2 PTs, 3 CTs 3bLn3 or 3bLL3
2-24
Figure 2-17 3-Wire 2-Element Direct Connection Using 2 CTs.
Wiring Mode = 3dir2