Menu operations, Basic device settings – E-Mon E-PS-A-RTU-N User Manual
Page 42

Chapter 3 Display
O P E R A T I O N S
M E N U O P E R A T I O N S
42
PowerSmart+ Advanced Power Quality Meter
If a number represents the parameter, adjust it to the desired value with the UP and DOWN
arrow buttons. When briefly pressed, the button increments or decrements the number by
one. When the button is pressed continuously, the number is changed approximately twice
per second.
If a name represents the parameter, select the desired option with the UP and DOWN
arrow buttons.
To store your new selection, press the ENTER button.
To leave the parameter unchanged, press the ESC button.
You will return to the parameter list to select another parameter or return to the main
menu.
To exit the menu, press ESC.
Menu Operations
Basic Device Settings
Basic Device Settings
Basic Device Settings
Basic Device Settings
This menu allows you to configure the basic meter settings that define the general
operating characteristics of the device. To enter the menu, select the “baSc” entry
from the main menu, and then press the ENTER button.
To select a setup option:
Press the SELECT button to activate the middle window.
Use the UP and DOWN arrow buttons to scroll to the desired option.
To change the option:
Press the SELECT button to activate the lower window.
Use the UP and DOWN arrow buttons to select the desired option.
Press ENTER to confirm your changes and to store your new setting, or press ESC to
discard changes.
To exit the menu, press ESC.
The following table lists available options.
Label
Parameter
Options
Default
Description
ConF
Wiring connection
(configuration) mode
See “Basic
Meter
Setup” in
Chapter 4
4Ln3
The wiring connection of the
device
Pt
PT ratio
1.0-6500.0
1.0
The phase potential
transformer’s primary to
secondary ratio
Pt.F
PT Ratio multiplier
Ч1, Ч10
Ч1
PT Ratio multiplication factor.
Used in extra high voltage
networks to accommodate the
PT ratio for 500 kV and higher
networks.
U.SEC
Nominal secondary
voltage
10-690 V
120 V
The nominal secondary line-to-
neutral (in 4LN3, 3LN3 and
3BLN3 wiring modes) or line-to-
line (in 4LL3, 3LL3, 3BLL3,
3OP2, 3OP3 and 3DIR modes)
voltage. Used as a reference
voltage for the EN50160
evaluation.
bASc
4Ln3
ConF
bASc
1.0
Pt
bASc
200.0
Pt
ENERGY
ENTER
SELECT
bASc
200.0
Pt
THD/TDD
ESC