E-Mon E-PS-A-RTU-N User Manual
Page 44

Chapter 3 Display
O P E R A T I O N S
M E N U O P E R A T I O N S
44
PowerSmart+ Advanced Power Quality Meter
Label Parameter
Options
Default
Description
P.cAL Power
calculation
mode
rEAc (reactive power),
nAct (non-active
power)
Reactive
The method used for
calculating reactive and
apparent powers
roLL
Energy roll
value
E
10.E4=10,000
10.E5=100,000
10.E6=1,000,000
10.E7=10,000,000
10.E8=100,000,000
10.E9=1,000,000,000
10.E9
The value at which
energy counters roll
over to zero
Ph.En Phase energy
option
E
diS = disabled
En = enabled
Disabled
Enables phase energy
calculations
bAtt
Backup battery
mode
OFF = switched OFF
On = switched ON
OFF
Allows to conserve a
battery while the meter
is out of operation
tESt
Energy test
mode
OFF = disabled
Ac.Ei = Wh pulses
rE.Ei = varh pulses
Disabled
Setting this option puts
the meter into the
energy test mode
An.EP Analog
expander
option
1
nonE = disabled
0-20 = 0-20 mA
4-20 = 4-20 mA
0-1 = 0-1 mA
-1-1 = ±1 mA
Disabled
Enables outputs for the
AX-8 analog expanders
through port COM2. See
“Analog Expander
Setup”
1
Do not enable the analog expander output if you do not have the analog expander
connected to the meter, otherwise it will disturb the computer communications.