Appendix f data scales – E-Mon E-PS-A-RTU-N User Manual
Page 149
![background image](/manuals/345952/149/background.png)
Appendix F Data Scales
PowerSmart+ Advanced Power Quality Meter
149
Appendix F Data Scales
The maximum values for volts, amps and power in the PowerSmart+ Advanced PQM setup
and in communications are limited by the voltage and current scale settings. See
Device
Options
in Chapter 4 on how to change the voltage scale in your meter.
The following table defines the meter data scales.
Scale
Conditions
Range
Maximum voltage
(V max)
All configurations
Voltage scale × PT Ratio, V
1
Maximum current
(I max)
All configurations
Current scale × CT Ratio, A
2, 3
Wiring 4LN3, 3LN3, 3BLN3
V max × I max × 3, W
Maximum Power
(P max)
4
Wiring 4LL3, 3LL3, 3BLL3,
3OP2, 3OP3, 3DIR2
V max × I max × 2, W
Maximum
frequency
50 or 60 Hz
100 Hz
1
The default voltage scale is 144V. The recommended voltage scale is 120V+20% = 144V
for using with external PT’s, and 690V+20% = 828V for a direct connection to power line.
2
CT Ratio = CT primary current/CT secondary current
3
The default current scale is 2
×
CT secondary (2.0A with 1A secondaries and 10.0A with 5A
secondaries)
.
4
Maximum power is rounded to whole kilowatts. With PT=1.0, it is limited to 9,999,000 W.