beautypg.com

Micromod MOD: 30ML Controller Operation and Maintenance Training Manual User Manual

Page 59

background image

Training Manual

MOD 30ML Diagnostics Lab

4 - 11

7

Press the NXT key to view Pages1,
2 3 and 4 and record the information

Shutdown page 2 displays the time and date of the
shutdown.

8

Press NXT to go to Page 5

Page 5 displays ACK SD and NO on lines 2 and 6
respectively. See the next figure:

Figure 4 .11.

8

Press the UP/DOWN arrow to show
YES

on line 6 and then press the key

next to EXT on the display

This will acknowledge the Shutdown and line 6 will
display NO again. Line 3 will now change to display
RUN. This means that the instrument state is back
to RUN.

.

The database we used for forcing the instrument to shutdown has a bug in the display
script for the PID. If you press the SCROLL key to switch between setpoint and output
for line 6 will force the instrument to shutdown again.

In certain cases where shutdown occurred due to serious hardware problems, you will still
be able to acknowledge the shutdown, but you nay not be able to put the instrument to
RUN mode. Call the MicroMod Automation Support at 585 321 9200 or visit

http://www.micromodautomation.com