beautypg.com

B.5 current consumption for models a and b – Micromod MOD: MODCELL Multiloop Processor 2002N Model C and Associated Hardware User Manual

Page 76

background image

MODCELL Multiloop Processor

APPENDIX B - SUMMARY OF HARDWARE DIFFERENCES

At least one cold junction compensation input is recommended for each controller to
sense the temperature at the terminal block. The CJIM module, Figure A-1, has been
replaced by a 2009AZ__2__ 2-wire RTD Input Module with RTD sensor as described
in Section 3.5.6 for cold junction compensation. CJIM input specifications are:

COLD JUNCTION COMPENSATION MODULE
Operating range: 0 to 50°C
Overrange: -20 to 70°C
Noise filter: 3 db at 4 Hz
Resolution: 16 bits
Sensitivity: 0.002°C
Accuracy: ±0.5°C
Isolation : 250 Vrms

Figure B-1.

Typical Input Circuit for 2010A Cold Junction Compensation Module

+

S18

BASE INSTRUMENT

LOWER

TERMINAL

HOUSING

1

2

Input

Circuitry

and A/D

Cold

Junction

Sensor

225S2

2010A COLD JUNCTION
COMPENSATION MODULE
(Module Location 18)

Processor

1

2

DATA

SEL

CLK

GND

+5 V

3

6

4

7

5

R

B

B.4

1706S CONFIGURATOR SUPPORT

The MODCELL configurator portion of the 1706S version 5.4 Configuration Software, as
described in IB-23H140, can be used to create (and download) up to a version 3 logic or
version 2 regulatory instrument configuration.

B.5

CURRENT CONSUMPTION FOR MODELS A AND B

The MODCELL Model A and B Instruments have the capacity to handle any mix of I/O that
uses 3.0 amps of current or less. Add the current consumption for each I/O module,
using the planning form in Appendix A, and verify that the total does not exceed 3.0
amps.

7

0