6 output connections – Micromod MOD: MODCELL Multiloop Processor 2002N Model C and Associated Hardware User Manual
Page 45

MODCELL Multiloop Processor
ELECTRICAL CONNECTIONS
3.6
OUTPUT CONNECTIONS
This section describes the process output connections for the following output module types:
•
2003A Current Output Module(Section 3.6.1)
•
2005A Solid-State Relay Output Module (Section 3.6.2)
•
2007A Nonisolated Digital Output Module (Section 3.6.3)
•
2011A Dual Mechanical Relay Output Module (Section 3.6.4)
•
2011A Form C Mechanical Relay Output Module (Section 3.6.5)
3.6.1 2003A Current Output (AOM)
Make current output connections as shown in Figure 3-9.
When the instrument is installed in the European Union, an interface filter must be
connected in the signal wires to the module to comply with European Union (EU)
Electromechanical (EMC) requirements. Use a Phoenix Contact FILTRAB NEF1-1 or
equivalent. Reference Phoenix Contact Ltd., P.O. Box 131, D32819, Blomberg, Lippe,
Germany, Phone 52-35-320510.
Output specifications are:
ANALOG OUTPUT
Range: (0-100%) 4 to 20 mA
Low limit: 0 mA
Upper limit: 25 mA
Open circuit voltage: 26 Volts maximum
Isolation : 250 Vrms
Resolution: 12 bits
Sensitivity: 5 uA
Accuracy: ±0.2% of span
S-3031-20
Figure 3-
8
. Typical Output Circuit for 2003A Current Output Module
S23
3
4 to 20
mA dc
BASE INSTRUMENT
2003A CURRENT OUTPUT MODULE
(Module Location 23)
+
–
LOWER
TERMINAL
HOUSING
1
2
Output
Load
Input
Isolation
Processor
D/A
V/I
+10V
Iso
DATA
SEL
CLK
GND
+5V
dc
4
7
6
5
1
2
39