beautypg.com

6 output connections – Micromod MOD: MODCELL Multiloop Processor 2002N Model C and Associated Hardware User Manual

Page 45

background image

MODCELL Multiloop Processor

ELECTRICAL CONNECTIONS

3.6

OUTPUT CONNECTIONS

This section describes the process output connections for the following output module types:

2003A Current Output Module(Section 3.6.1)

2005A Solid-State Relay Output Module (Section 3.6.2)

2007A Nonisolated Digital Output Module (Section 3.6.3)

2011A Dual Mechanical Relay Output Module (Section 3.6.4)

2011A Form C Mechanical Relay Output Module (Section 3.6.5)

3.6.1 2003A Current Output (AOM)

Make current output connections as shown in Figure 3-9.

When the instrument is installed in the European Union, an interface filter must be
connected in the signal wires to the module to comply with European Union (EU)
Electromechanical (EMC) requirements. Use a Phoenix Contact FILTRAB NEF1-1 or
equivalent. Reference Phoenix Contact Ltd., P.O. Box 131, D32819, Blomberg, Lippe,
Germany, Phone 52-35-320510.

Output specifications are:

ANALOG OUTPUT

Range: (0-100%) 4 to 20 mA
Low limit: 0 mA
Upper limit: 25 mA
Open circuit voltage: 26 Volts maximum
Isolation : 250 Vrms
Resolution: 12 bits
Sensitivity: 5 uA
Accuracy: ±0.2% of span

S-3031-20

Figure 3-

8

. Typical Output Circuit for 2003A Current Output Module

S23

3

4 to 20

mA dc

BASE INSTRUMENT

2003A CURRENT OUTPUT MODULE
(Module Location 23)

+

LOWER

TERMINAL

HOUSING

1

2

Output

Load

Input

Isolation

Processor

D/A

V/I

+10V

Iso

DATA

SEL

CLK

GND

+5V

dc

4

7

6

5

1

2

39