beautypg.com

Micromod MOD: MODCELL Multiloop Processor 2002N Model C and Associated Hardware User Manual

Page 24

background image

MODCELL Multiloop Processor

MECHANICAL INSTALLATION

Table 2-1. Module Types and Suggested Locations

Block

Type

Module Type

Module Location

1 to 16

17 to 32

VCIM

2001A Voltage Input
2002A Current Input
2012A Current Input with 2-Wire Transmitter

Note 1

X

RIM

2009A RTDInput (2 Wire)

Note 1

X

WRIM

2009A RTDInput (3 Wire)

Note 1

Note 3

TIM

2013A Thermocouple Input
with Upscale Burnout Detection

Note 1

X

AOM

2003A Current Output

Note 1

X

DIM

2004A Solid State Relay Input
2006A Nonisolated Digital Input

X

Note 2

DOM

2005A Solid State Relay Output
2007A Nonisolated Digital Output

X

Note 2

DDOM

WDOM

2011A Mechanical Relay Output (SPST)
2011A Mechanical Relay Output (Form C)

Note 3

Notes 2,

3

RIO

2020N Remote I/O Interface

Note 3

Note 3

ICN

2030N ICN Communication

–––––––––

Note 4

MSC

2033N RS-232 Communication
2032N RS-485 2-Wire Communication
2034N RS-485 4-Wire Modbus Communication

____

Note 5

Notes:
1.

These locations can be used for analog modules if locations 17 - 32 are occupied.

2.

These locations can be used for discrete modules if locations 1 - 16 are occupied.

3.

Module occupies two locations.

4.

ICN Module occupies two locations and may be in locations 25 through 32 only.

5.

RS-232 Module and RS-485 4-Wire Module are double wide modules that can occupy
slots 31-32 (Port 1), 28-29 or 29-30 (Port 2), 25-26 or 26-27 or 27-28 (Port 3).
RS-485 2-Wire Module is a single wide module that can occupy slot 32 (Port 1), 29 or
30 (Port 2), 26 or 27 or 28 (Port 3).

! CAUTION

Module group S25 to S32 is reserved for modules whose circuits are rated less than
30V rms 42.4V peak or 60Vdc. Module locations within a group (S1 to S8, S9 to S16
and S17 to S24) must all be rated less than 30V rms or 42.4V peak or 60Vdc or must
all be rated for greater than 30V rms or 42.4V peak or 60Vdc.Do not mix modules
employed in circuits rated less than 30 V rms or 42.4V peak or 60Vdc with modules
used in circuits greater than 30V rms or 42.4V peak or 60Vdc within the same group.

WARNING

Do not use any I/O module which i s not listed in Instruction Notice 92902-98 (back of
book). When used in flush mount controller, the listed modules are FM Approved and
CSA Certified for use in Class I, Division 2, Group A, B, C or D hazardous (classified)
locations. Substitution of a module not on the list voids the Approval/Certification.

WARNING

Do not use a 2011A Mechanical Rel ay Output Module when the installation
environment contains chemicals which can degrade the materials used to seal the
relay in the module. The sealing materials are as follows:
• Polybutylene Terephthalate, Po lyplastics Co. Ltd., Compound No. 3270
• Polyphelene Suffide, Summitomo Chemical Co. Ltd., Compound No. 3601GL30
• Epoxy Resin, Summito Bakelite Co. Ltd., SUMIMAC ECR-9107K
Degradation of the relay seal voi ds the Approval/Certification of the instrument for use
in Class I, Division 2, Group A, B, C or D hazardous (classified) locations.