MODCELL Multiloop Processor

ELECTRICAL CONNECTIONS

3.6.5 2011A Form C Mechanical Relay Outputs (WDOM)

Make mechanical relay output connections as shown in Figure 3-14.
Wire rating: 600 V, -20°C +105°C UL, CSA approved. Output specifications are:

FORM C MECHANICAL RELAY OUTPUT

Configuration

Form C single relay

Power supply range

+ 5 VDC ±10%

Max Input Current

-10.0 mA DC

Contact rating - 2011AZ10...

3A at 250 VAC or 30 VDC

Contact rating - 2011AZ12...

3A at 60 V rms or 30 VDC

Contact resistance

0.10 ohms maximum

Isolation

250 Vrms (contacts to coil)

Response time

10 msec

Figure 3-1

3

.

Typical Output Circuit for 2011AZ__200A Mechanical Relay Output Module (Form C)

NO

NC

S1

S2

+

14

BASE INSTRUMENT

2011A MECHANICAL
RELAY OUTPUT
MODULE (Locations 1
and 2)

Output

Load

UPPER

TERMINAL

HOUSING

1

2

External

Power
Supply

1

2

Base

Instrument

1

2

13

3

4

15

16

WARNING

Do not use a 2011A Mechanical Rel ay Output Module when the installation
environment contains chemicals which can degrade the materials used to seal the
relay in the module. The sealing materials are listed on page 18. Degradation of the
relay seal voids the Approval/Certification of the instrument. Required for use with
2002NZ12...

4