3.5.2 2004A SSR Input (DIM)

Make Solid-State Relay (SSR) connections as shown in Figure 3-4. These input modules
are used for sensing ON/OFF voltage levels. Each module provides optical isolation
between the field devices and the control logic. This isolation is limited to 250 Vrms at the
terminal block. Typical uses and applications for these input modules include sensing
voltage and contact conditions from: proximity switches, limit switches, selector switches,
push buttons, photoelectric switches, TTL compatible devices, float switches, or
thermostats.

Wire rating: 600 V, -20°C +105°C UL, CSA approved.

Input specifications are:

DIGITAL INPUTS (ISOLATED)

_10_

_11_

_12_

Input voltage ranges

2.5-28Vdc

4-16Vdc

10-32Vdc, 12-32Vac

mA Input current at Max Line

30

45

25

Max Logic Low Input

1V, 0.2 mA

1V, 0.7 mA

3V, 1 mA

Input Resistance (Ohms)

900

300

1K (dc), 1.5K (ac)

Module Response Time (msec)

1.5

0.1

5

DIGITAL INPUTS (ISOLATED)

_13_

_14_

_15_

Input voltage ranges

35-60Vac/dc

90-140Vac/dc

180-280Vac/dc

mA Input current at Max Line

6 (dc), 25 (ac)

11

7

Max Logic Low Input

9V, 0.8 mA

45V, 3 mA

80V, 1.7 mA

Input Resistance

10K Ohms

14K Ohms

43K Ohms

Module Response Time (msec)

10 (dc), 15 (ac) 20

20

30