beautypg.com

Micromod MOD: MODCELL Multiloop Processor 2002N Model C and Associated Hardware User Manual

Page 49

background image

MODCELL Multiloop Processor

ELECTRICAL CONNECTIONS

3.6.4 2011A Dual Mechanical Relay Outputs (DDOM)

Make mechanical relay output connections as shown in Figure 3-13.
Wire rating: 600 V, -20°C +105°C UL, CSA approved. Output specifications are:

DUAL MECHANICAL RELAY OUTPUTS

Configuration

Dual relays (NO/NO, NC/NC, NO/NC)

Power supply range

+ 5 VDC ±10%

Max Input Current

-10.0 mA DC

Contact rating - 2011AZ10...

3A at 250 VAC or 30 VDC

Contact rating - 2011AZ12...

3A at 60 V rms or 30 VDC

Contact resistance

0.10 ohms maximum

Isolation

250 Vrms (contacts to coil)

Response time

10 msec

Figure 3-1

2

.

Typical Output Circuit for 2011A Mechanical Relay Output Module (Dual SPST, NO/NC)

S5

S6

+

14

BASE INSTRUMENT

Output

Load

2011A MECHANICAL
RELAY OUTPUT
MODULE (Module
Locations 5 and 6)

Output

Load

UPPER

TERMINAL

HOUSING

1

2

External

Power
Supply

1

2

External

Power
Supply

Base

Instrument

Output Logic

Channel 1

Note:

1. Other module

forms are NC/NC
and NO/NO.

1

2

13

3

4

+

15

16

Base

Instrument

Output Logic

Channel 2

WARNING

Do not use a 2011A Mechanical Rel ay Output Module when the installation
environment contains chemicals which can degrade the materials used to seal the
relay in the module. The sealing materials are listed on page 18. Degradation of the
relay seal voids the Approval/Certification of the instrument. Required for use with
2002NZ12...

4

3