beautypg.com

Micromod MOD: MODCELL Multiloop Processor 2002N Model C and Associated Hardware User Manual

Page 46

background image

MODCELL Multiloop Processor

ELECTRICAL CONNECTIONS

3.6.2 2005A SSR Output (DOM)

Recommended connections to a customer relay are shown in Figure 3-10. Make SSR
output connections as shown in Figure 3-11. Note: (*) indicates module may be operated
at 2 amps only if there is no module on either side of this module.

DC output modules are used for controlling or switching DC loads. Each module provides
optical isolation between the field devices and the control logic. This isolation is limited to
250 Vrms at the terminal block. Typical uses and applications for DC output modules
include switching the following loads: DC relays, DC Solenoids, DC motor starters, or DC
lamps or indicators. Wire rating: 600 V, -20°C +105°C UL, CSA approved.
Module Fuse rating: 4 Amps, 250V.

DC DIGITAL OUTPUTS (ISOLATED)

_10_

_11_

Output voltage ranges

5-60 V

5-200 V

Max Output current

1A*

0.55A

Turn-off time

0.75 msec

0.75 msec

Max Output voltage drop

1.6 V

1.6 V

Off-state leakage at max V

1 mA

2 mA

AC output modules are used for controlling or switching AC loads. Each module provides
optical isolation between the field devices and the control logic. This isolation is limited to
250 Vrms at the terminal block. Typical uses and applications for AC output modules
include switching the following loads: relays, solenoids and contactors, motor starters,
heaters, lamps, or indicators. Wire rating: 600 V, -20°C +105°C UL, CSA approved.
Module Fuse rating: 4 Amps, 250V.

AC DIGITAL OUTPUTS (ISOLATED)

_12_

_13_

_14_

Output voltage range

12-140 V

24-280 V

24-280 V

Max Output current

1A*

1A*

1A*

Off-state leakage

5 mA

5 mA

5 mA

(2.5 at 120V)

Minimum load current

20 mA

20 mA

20 mA

Response time

1/2 cycle

1/2 cycle

1/2 cycle

Max Output voltage drop

1.6 V

1.6 V

1.6V

Form

A (Make)

A (Make)

B (Break)

Type

SPST-NO

SPST-NO

SPST-NC

S7

SOLID STATE RELAY OUTPUT

CONTROLLER

L

N

AC Power

Customer’s

External

Relay

1

2

Figure 3-

9

. Recommended Connection to Solid State Relay

4