Table 4-4. analog output (ano) module – Micromod Micro-DCI: 53ML5100A LOADING STATION User Manual

Page 44

background image

Table 4-4. Analog Output (ANO) Module

Purpose: The primary purpose of this module is to select and set the 0 - 20 mA or 4 - 20 mA
output signals for ANO0 and ANO1.

Title

Symbol

ANO

ANO0

Data-
point

De-

fault

Attribute

Analog
Output
(Display
Only)

ANO0
ANO1

ANO0
ANO1

C000
C001

0
0

The value in this datapoint represents the
percent of output to be generated by hardware
(e.g., 100% output = 20 mA).

0 - 20 mA
Output

OZBASE0
OZBASE1

ANO0
ANO1

L472
L473

0
0

When a 0, the percentage output generates a 4 -
20 mA signal. When set to 1, the percentage
output generates a 0 - 20 mA signal.

Calibrate
Zero

COZ0
COZ1

ANO0
ANO1

B267
B268

These parameters are factory set and should
not need
adjustment under normal operation.
See Section 5.3 for calibration information.

Calibrate
Span

COS0
COS1

ANO0
ANO1

C300
C301

Reverse
Valve

RSV0
RSV1

ANO0
ANO1

L109
L133

0
0

It positions the forward/reverse valve indicators
(C for close, O for open) beneath the output
horizontal bar graph of each Manual Loader with
Analog Input Display (Channel 1 and Channel
2). When set to a 0, it indicates 20 mA output
opens the valve (C at left end and O at right end
of bar graph). When set to a 1, it indicates 20
mA output closes the valve (O at left end and C
at right end of bar graph).

Control
Action

ANO0
ANO1

L106
L130

0
0

When set to a 0, current increases toward 20
mA to open the valve more as the output
indicator increases when the push button
is pressed.
When set to a 1, current decreases toward 0 mA
to close the valve as the output indicator
increases when the push button is
pressed.

Engineerin
g Units

ANO0
ANO1

A001
A003

PERCE

NT

(Both)

It is assignable for units of measure the ANO
represents (e.g., GPM for gallons per minute).

Tag
Name

AOTAG0
AOTAG1

ANO0
ANO1

A244
A245

ANO0
ANO1

An assignable 10 character name for each ANO
(ANO0 and ANO1).

Section 4. Configuration Parameters