Table 4-4. Analog Output (ANO) Module
Purpose: The primary purpose of this module is to select and set the 0 - 20 mA or 4 - 20 mA
output signals for ANO0 and ANO1.
Title
Symbol
ANO
ANO0
Data-
point
De-
fault
Attribute
Analog
Output
(Display
Only)
ANO0
ANO1
ANO0
ANO1
C000
C001
0
0
The value in this datapoint represents the
percent of output to be generated by hardware
(e.g., 100% output = 20 mA).
0 - 20 mA
Output
OZBASE0
OZBASE1
ANO0
ANO1
L472
L473
0
0
When a 0, the percentage output generates a 4 -
20 mA signal. When set to 1, the percentage
output generates a 0 - 20 mA signal.
Calibrate
Zero
COZ0
COZ1
ANO0
ANO1
B267
B268
These parameters are factory set and should
not need adjustment under normal operation.
See Section 5.3 for calibration information.
Calibrate
Span
COS0
COS1
ANO0
ANO1
C300
C301
Reverse
Valve
RSV0
RSV1
ANO0
ANO1
L109
L133
0
0
It positions the forward/reverse valve indicators
(C for close, O for open) beneath the output
horizontal bar graph of each Manual Loader with
Analog Input Display (Channel 1 and Channel
2). When set to a 0, it indicates 20 mA output
opens the valve (C at left end and O at right end
of bar graph). When set to a 1, it indicates 20
mA output closes the valve (O at left end and C
at right end of bar graph).
Control
Action
ANO0
ANO1
L106
L130
0
0
When set to a 0, current increases toward 20
mA to open the valve more as the output
indicator increases when the push button
is pressed.
When set to a 1, current decreases toward 0 mA
to close the valve as the output indicator
increases when the push button is
pressed.
Engineerin
g Units
ANO0
ANO1
A001
A003
PERCE
NT
(Both)
It is assignable for units of measure the ANO
represents (e.g., GPM for gallons per minute).
Tag
Name
AOTAG0
AOTAG1
ANO0
ANO1
A244
A245
ANO0
ANO1
An assignable 10 character name for each ANO
(ANO0 and ANO1).
Section 4. Configuration Parameters