3 engineering mode overlays, Table 3-1. entering a key password – Micromod Micro-DCI: 53ML5100A LOADING STATION User Manual

Page 29

background image

3.3 ENGINEERING MODE OVERLAYS

The engineering mode overlays are used to make the necessary parameter entry selections for the
operator displays. The entries are made to addressed datapoints via the overlay single edit line at
the bottom of the display. It should be noted that engineering mode has a 20 second timeout if it is
accessed and its functions (e.g., configure or display) are not used.

3.3.1 RESPONDING TO THE PROMPT KEY?

When the password prompt KEY? appears, it indicates a password was set with an external device
(e.g. Hand Held Configurer, PC, etc.). The password can not be set via the front panel push but-
tons. A password key is a maximum of 10 numeric characters (numbers 0-9 only). It does not im-
pede display functions in engineering mode but must be unlocked to perform configuration
functions. A password key is NOT SET FOR NEW INSTRUMENTS from the factory; therefore, if it
is set, it must have been done locally. The password must first be obtained from the originator be-
fore the procedure in Table 3-1 can be used to access the engineering mode configuration function
capabilities. Figure 3-8 illustrates the CONFIGURE prompt, the KEY? prompt, the key 222222 en-
tered on the edit line, and the POINT input query.

Table 3-1. Entering a Key Password

Step

Press

Once

Shift

Result

Press to

Locate

Target

Char.

Result

1

z

Puts instrument in engineering mode.

2

If DISPLAY appears instead of CONFIGURE, press 2.

3

3

Displays password query: KEY? .

4

2

Puts first password number on entry line:
KEY? .2.

5

.2

2

Shifts 2 and puts second password number on
entry line: KEY? .22.

6

.22

2

Shifts 22 and puts third password number on
entry line: KEY? .222.

7

Repeat step 6 until all of the password characters are entered.

8

3

It enters the password key and displays the entry
line: POINT . The engineering mode
configuration function is now accessible for use.

Note:

= space.

53ML5100 Manual Loading Station

3-6