Table 1-1. Specifications

Item

Specification(s)

Environmental Characteristics
Controlled Environment

Ambient Temperature Limits

Relative Humidity Limits

Temperature Effects on Accuracy

Transient Immunity (all circuits)

EMI Susceptibility

Enclosure Classification/Environment

Shock

Vibration

Drop and Topple

Enclosed temperature controlled location (Class
A and B per ISA-S71.01 1985)

4 - 52

°

C (40 - 125

°

F)

10 - 90% maximum

±

0.28% per 28

°

C (50

°

F) change from reference

temperature 25

°

C (77

°

F)

ANSI C37.90a - 1974/IEEE Std 472-974:
Ring Wave: 1.5 MHz, 3 kV, 60 pulses/s for 2.0 s

SAMA PMC 33.1-1978: Class 3-abc: no effect
at 30 V/m, at 27, 146, and 446 MHz

Panel Mounted Equipment: No enclosure
rating. Designed to be installed in a user
provided panel or enclosure.

Rated for installation in a Pollution Degree 2
location per U.L. 508-1989/Controlled
Environment
per CSA C22.2 No. 142-M1987.
An indoor, temperature controlled location
(Control Room or Shop Floor) where normally
only non-conductive pollution occurs; however,
temporary conductivity caused by condensation
may be expected.

Location in environments more severe than
those stated requires supplementary protection.

0.5 g

SAMA PMC 31.1-1978: peak-to-peak constant
displacement 0.05 in. (1.27 mm), 5-14 Hz:
0.5 g, 14-200 Hz.

SAMA PMC 31.1-1978: Tilt 30 degrees from
horizontal and fall freely to a hard surface, all
sides, front, and back.

53ML5100 Manual Loading Station