beautypg.com

Liquid Controls SP3850 User Manual

Page 38

background image

SP3850 Flow Computer

34

ENTER

ENTER

ENTER

ENTER

ENTER

6.3.14 (Continued)
SETUP RELAYS
(Relay 3 & Relay 4)

ENTER

SETUP RELAYS
Rly1 Rly2

Rly3 Rly4

RELAY 3 USAGE
Rate Tot Aux Ovr NA

RELAY 4 USAGE
Rate Tot Aux Alrm NA

ASSIGN AUX CHANNEL
AUX 1 AUX 2

RELAY 3 DELAY sec
0

RELAY 3 MODE
LO_ALARM HI_ALARM

RELAY 3 DURATION

#####

RELAY 3 SETPOINT

####### gal

RELAY 3 HYSTERESIS

##### gal/m

Advance To

SETUP CONTROL INPUTS

Select the desired Relay for setup.
(Relays 3 & 4 Optional)

If Relay 3 Selected,
Choose Rate, Total, Aux, Ovr or NA.

If Relay 4 Selected,
Choose Rate, Total, Aux, Alrm or NA.

If Aux selected, enter desired auxilliary
channel.

If Rate / Aux selected, enter desired relay
activation delay value.

Select the desired Relay Activation for Rate/Aux.
Low: Relay activates when reading is below

setpoint.

High:Relay activates when reading is above

setpoint.

If Total Selected, Enter desired Relay
Duration.

Enter the desired Setpoint.

If Rate, selected, Enter desired Relay
Hysteresis.

NOTE:

Settings for Relays
3 & 4 may be
entered even if
relays are not
supplied. The
settings will still
trigger display
alarms.

Sub-menus

Display

Notes

ENTER

RELAY NOTES & CONSIDERATIONS

1. Relay activation is based on the computed readings not the displayed value. Therefore the display

damping factor will not affect the relay response time. The RELAY DELAY feature allows the user
to enter a time delay for relay activation. This feature is very useful in applications where short over/
under range conditions are not considered alarm conditions.

2. When INSTRUMENT TYPE is set to batcher, Relay 1 is reserved for PRESET and Relay 2 is

reserved for PREWARN.

3. Setting the relays to NA (Not Assigned), will allow the relay activation to be controlled via the RS-

232 Serial and/or RS-485 Modbus ports.

4. Relay 3 and Relay 4 settings may be used to trigger display alarm conditions even if the relays are

not supplied.

ENTER