SP3850 Flow Computer

6.3.8
SETUP
FLOW INPUT

SETUP FLOW INPUT

EXCITATION VOLTAGE
5v 12v 24v

PULSE INPUT TYPE
ChA A=B Qx1 U/D

PULSE TRIGGER LEVEL
10mV 100mV 2.5V

LOW PASS FILTER
40Hz 3KHz 20KHz

INPUT TERMINATION
Pullup Pulldown None

MAX WINDOW (1-99)

1 sec

K_FACTOR TYPE
AvgK LinTbl UVC StRo

AVERAGE KA-FACTOR

####### P/gal

AVERAGE KB-FACTOR

####### P/gal

CHANGE TABLE A

Yes

N0

LINEAR TABLE KA

Fre01:######## Hz

LINEAR TABLE KA
KA--01:####### P/gal

CHANGE TABLE B

Yes

N0

LINEAR TABLE KB
Fre01:######## Hz

LINEAR TABLE KB
KB--01:####### P/gal

LINEAR TABLE KA
Fre01:######## Hz/ck

LINEAR TABLE KA
KA--01:####### P/gal

LINEAR TABLE KB
Fre01:######## Hz/ck

LINEAR TABLE KB
KB--01:####### P/gal

Continued On Next Page

ENTER

Press ENTER to begin setup of Flow Input.

Select the desired Excitation Voltage.

Enter the desired Pulse type. See side note.

Select the desired Input Pulse Trigger Level.

Select the desired Low Pass Filter.
(Max. Count Speed).

Select the proper input termination.

Enter the desired Maximum Sample Window
Time (1-99 sec).

Enter the desired K-Factor Type. See side
note.

If Avg selected, Enter the desired Average K-
Factor (KA for channel A).

Enter the desired Average K-Factor (KB for
channel B).

If LinTbl selected, Select YES to change table
Enter the desired frequency/ K-Factor pair (in
ascending order) for each point in the
Linearization Table. (channel A)
NOTE: Enter 0 for Fre value of any point (other

than Fre01) to exit the routine and use
the values entered up to that point.

Enter the desired frequency/ K-Factor pair (in

ascending order) for each point in the
Linearization Table. (channel B)

NOTE: Enter 0 for Fre value of any point (other

than Fre01) to exit the routine and use
the values entered up to that point.

If UVC selected, Select YES to change table
Enter the desired Hz/ck/ K-Factor pair (in
ascending order) for each point in the
Linearization Table. (channel A)
NOTE: Enter 0 for Hz/ckvalue of any point

(other than Hz/ck01) to exit the routine
and use the values entered up to that
point.

Enter the desired Hz/ck/ K-Factor pair (in
ascending order) for each point in the
Linearization Table. (channel B)
NOTE: Enter 0 for Hz/ck value of any point

(other than Hz/ck01) to exit the routine
and use the values entered up to that
point.

Submenus

Display

Notes

Through

40 Points

ENTER

ENTER

ENTER

Through

40 Points

NOTE:

ChA = Single Pulse
A=B = Pulse Security
Qx1 = Quadrature
U/D = Up/Down Control

Line

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

NOTE:
AvgK =

Average
K-Factor

LinTbl = Linearization

Table

UVC =

Universal
Viscosity
Curve

StRo =

Strouhal
Roshko Curve

ENTER

ENTER

Through

40 Points

Through

40 Points