Signet 2250 hydrostatic level sensor setup, Signet 2350 temperature sensor setup – GF Signet 3-0250 USB to Digital (S3L) Configuration-Diagnostic Tool User Manual

Page 6

background image

6

Signet 0250 Setup Tool

Windows PC

USB

GND

Data

+5V out

Signet 2250

Hydrostatic

Level Sensor

GND

Data

+5V

Signet 2250 Hydrostatic Level Sensor Setup

2250 Wiring

2250 Operation
1. Select the engineering units for the application: inches,

feet, centimeters or meters.

2. Set the Level measurement where the Loop output must

equal 4 mA.

3. Set the Level measurement where the Loop output must

equal 20 mA.

• Minimum setting for both endpoints is 0.
• Maximum setting for both endpoints is based on the

maximum pressure rating of the sensor.

• Maximum setting, -XU sensor (0-10 psi)
• 7.03 m = 703.1 cm = 23.07 ft. = 276.8 in.
• Maximum setting, -XL sensor (0-50 psi)
• 35.15 m = 3515.0 cm = 115.33 ft. = 1384.0 in.

4. Click "Write" to copy settings from the display into the

Magmeter.

Click "Save" to save the settings from the display to a
computer fi le.

5. To use a saved fi le:

• Click "Load"
• Navigate to the saved fi le
• Select Open
• Click "Write"
• Click "Read" to confi rm

Signet 2350 Temperature Sensor Setup

Windows PC

Signet 2350

Temperature

Sensor

USB

GND

Data

+5V out

GND

Data

+5V

2350 Wiring

2350 Operation
1. Select the engineering units for the application:

°C (Celsius) or °F (Fahrenheit).

2. Set the Temperature measurement where the Loop output

must equal 4 mA.
• Minimum setting -10 °C (14 °F)
• Maximum setting 100 °C (212 °F)

3. Set the Temperature measurement where the Loop output

must equal 20 mA.

• Minimum setting -10 °C (14 °F)
• Maximum setting 100 °C (212 °F)

4. Click "Write" to copy the settings from the display into the

Magmeter.

OR

Press "Save" to save the settings from the display to a
computer fi le.

To use a saved fi le:
• Click "Load"
• Navigate to the saved fi le
• Select Open
• Click "Write"
• Click "Read" to confi rm.