Signet 2610 Process Optical Dissolved Oxygen Sensor

3-2610.091

Rev. A 04/12 English

*3-2610.091*

English

MODBUS Manual

Cable length must not exceed 1220 m (4000 ft)

Power Connections

The red wire provides power for all system modes. Analog output
is enabled by default. The 4 to 20 mA current loop output can be
disabled by setting Modbus device register 49507 to 0. Set it back
to 1 to re-enable the 4 to 20 mA loop.

RDO is a registered trademark of In-Situ

®

Inc., Fort Collins, CO USA

The RDO

®

Pro sensor may be connected to a controller or

logger for communication via RS485 Modbus.

Trim back and insulate unused wires. The shielded wire should be
wired to a chassis ground or earth ground.

Red

Black

Blue

Green

Brown

White

+

Modbus

RS485

Modbus

RS485

3-2610-31

RDO Pro Dissolved Oxygen

Programmable Logic Controller

or

Other Modbus Master

+

Power

Supply

12 to 36 VDC

PLC

No connection

Red

Black

Blue

Green

Brown

White

Power Supply, 12 to 24 VDC +

Power Supply, 12 to 24 VDC –

Modbus RS485 +

Modbus RS485 –
4 to 20 mA Current Loop

SDI-12 Output

3-2610-31

RDO Pro Dissolved Oxygen