beautypg.com

Adjustment of the micro switches or the proximity, Switches (option) – Burkert Type 8697 User Manual

Page 27

background image

27

Electrical installation

Version with
three-wire
proximity
switches

Version with
two-wire
proximity
switches

Version with
two-wire
proximity
switches by
namur (ex
version)

5)

end position
top

LED Top

is lit yellow

is lit yellow

goes out

end position
bottom

LED Bottom

is lit yellow

is lit yellow

goes out

Fig. 24: End position LED yellow

The version with micro switches (mechanical limit switches) does
not include any LED to indicate position.

5)

In the case of the version with 2-conductor initiators according
to NAMUR the LED function is inverse for technical reasons, i.e.
the LED glows when the end position is not reached and goes
out when the end position is reached.

9.5.

adjustment of the micro switches
or the proximity switches (option)

Danger!

risk of electric shock.

▶ Before reaching into the device, switch off the power supply and

secure to prevent reactivation.

▶ Observe applicable accident prevention and safety regulations

for electrical equipment.

procedure:

Open the Pneumatic Control Unit: unscrewing the transparent cap
in an anticlockwise direction.

Ensure that the distance between both switch cams is maximum.
(see “7. Installation”).

Switch spindle

Switch cam

3

Spacer sleeve

Maximum

distance

Fig. 25: Distance between the switch cams

english

Type 8697