beautypg.com

Burkert Type 8697 User Manual

Page 24

background image

24

Electrical installation

9.2.2. connection diagram

with three-wire proximity switches
(inductive limit switches)

terminal configuration

external circuit

1

INI + (24 V DC)
Supply

4

3

2

1

Output 2
(24 V)

Output 1
(24 V)

GND

+24 V DC

2

INI GND
Supply

3

INI Top OUT
Output 1

4

INI Bottom OUT
Output 2

5

Valve control
0 / 24 V DC

5

6

0 / 24 V DC ± 10 %
Residual ripple 10 %

6

Valve control
GND

Tab. 3: Connection diagram with three-wire proximity switches

Screw terminals

1
2

3

Terminal No

4
5

6

Fig. 19: Position of the screw terminals

9.2.3. connection diagram

with two-wire proximity switches
(inductive namur limit switches)

terminal configuration external circuit

1

INI Top +

NAMUR-
Sensor

Explosion

protected area

Non-hazardous
area

+8,2 V DC

0 V

R

1 / 3

2 / 4

2)

2

INI Top -

3

INI Bottom +

4

INI Bottom -

5

Valve control
+

5

6

3)

6

Valve control
GND

Tab. 4: Connection diagram with two-wire proximity switches

2)

(Recommended by NAMUR) Observe the max. values of the
intrinsically safe circuits in the ATEX additional instructions.

3)

Signal from barrier see PTB 07 ATEX 2048

english

Type 8697