Saving parameter, Transmission of the actual position, Transmission of the actual position 11 – BEI Sensors MHK5 Absolute Hollow Shaft Encoder User Manual
Page 11: Device net user manual

DEVICE NET USER MANUAL
BEI IDEACOD SAS
Espace Européen de l’Entreprise
9, rue de Copenhague
B.P. 70044 Schiltigheim
F 67013 Strasbourg Cedex
Tél
: +33 (0)3 88 20 80 80
Fax : +33 (0)3 88 20 87 87
Mail :
Web : www.bei-ideacod.com
4.3. Saving Parameter
The parameters of the absolute rotary en-
coder are saved in a non-volatile FLASH
memory. Because of a limited number of writ-
ing cycles ( 1,000), it is useful to transmit the
modified parameter in the first step only in the
RAM area. After adjusting and examination,
those values can be saved in the FLASH mem-
ory. After successful saving of the parameter
the encoder sends his MAC-ID on the bus. To
get the process value a new allocation of the
slave is required.
Example:
(MAC-ID Master: 0A hex, MAC-ID Slave: 03
hex)
5. Transmission of the actual position
The process value is transmitted according to
the following table.
CAN-ID
process value
11 Bit
Byte 0
Byte 1
Byte 2
Byte 3
2
7
to 2
0
2
15
to 2
8
2
23
to 2
16
2
31
to 2
24
Byte
Offset
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Frag [0]
XID
MAC ID
1
R/R [0]
Service [32]
Class ID [23]
Instance ID [01]
CAN-ID Byte 0 Byte 1
Byte 2
Byte 3
41C
0A
32
23
01
Version 05/04
UME-OCD-D2