Physical Data
Model UGW Module and Compressor
80
Capacity (Tons)
1
77
Refrigerant Type
R-134a
Compressor kWi
53.75
kW/Ton @ Full Load
0.698
Compressor Type
Optimized Quiet Screw
Compressor Quantity
1
Compressor Nominal HP
80
Refrigerant Charge (lbs)
119
Oil Circulation Rate
<0.5%
Module Operating Weight w/Water (lbs)
2
3,422
Module Shipping Weight (lbs)
3
2,995
Heat Exchanger (Type)
Brazed Plate
Refrigerant Circuits (quantity)
1
Water Storage Volume HX Only (gals.)
11.2
Water Storage Volume HX Plus 8" Main Headers (gals.)
26.4
Maximum Working Design Pressure-Water Side (PSI)
300
Header Water Connections - Inlet/Outlet (inches)
4
8
Heat Exchanger (Type)
Brazed Plate
Refrigerant Circuits (quantity)
1
Water Storage Volume HX Only (gals.)
14.9
Water Storage Volume HX Plus 8" Main Headers (gals)
30.1
Maximum Working Design Pressure - Water Side (PSI)
300
Header Water Connections - Inlet/Outlet (inches)
4
6
Notes:
4. Main header water/fluid connections are 8" grooved coupling.
5. Utilize Selection Program for performance based on glycol solution.
2. Module operational weight includes water, compressor oil, and refrigerant charge. Multiply times the number of modules for a total sytem operational weight.
3. Module shipping weight includes refrigerant charge, compressor oil and packaging.
Model UGW Evaporator
Model UGW Condenser
1. Tonnage ratings conditions: 44°F leaving chilled water temperature, 85°F entering condenser water temperature, flow rates are 3 GPM per ton through the condenser with a fouling
factor of .00025 and 2.4 GPM per ton through the evaporator with a .0001 fouling factor.
Notes:
a .0001 fouling factor.
a total system operational weight.
4. Main header water/fluid connections are 8" grooved coupling.
5. Utilize Selection Program for performance based on glycol solution.
2. Module operational weight includes water, compressor oil, and refrigerant charge. Multiply times the number of modules for
3. Module shipping weight includes refrigerant charge, compressor oil and packaging.
1. Tonnage ratings conditions: 44°F leaving chilled water temperature, 85°F entering condenser water temperature, flow rates are
3 GPM per ton through the condenser with a fouling factor of .00025 and 2.4 GPM per ton through the evaporator with