Control access display table, Local access display table, System setup fn2 – ClimaCool UGW Manual User Manual
Page 31

29
www.climacoolcorp.com
Control Access Display Table
Page 2 of 15
10/9/2013
Product Line: UGW
Software Version: UGW-H.08B.13
Chiller Type: COOLING 4 PIPE
LOCAL ACCESS DISPLAY TABLE
/Unit Mode:
Unit Mode
unit_mode_1
Normal Run
Schedule,
NoFlo/Phas,
CHWR High,
CWS Low, Sens
Error,
NoModAvail,
Module Dwn,
Compr Dwn,
NonCritAlm,
Normal Run
FALSE
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
EVAP STATUS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
Evap Water Temp & Pump Status
Evp H2O In: (F)
CHWR In Temp Status
chwr_stat_1
54.4
FALSE
/Evp WaterOut: (F)
CHWS Out Temp Status
chws_stat_1
50.2
FALSE
Evap Flow Status:
Evap Flow SW
evap_flow_1
On
Off, On
FALSE
Ev Pmp#1 Status:
CHW Pump 1 S/S
chw_pump_1_ss_1
Off
Off, On
FALSE
/Ev Pmp#2 Status:
CHW Pump 2 S/S
chw_pump_2_ss_1
Off
Off, On
FALSE
Chil Water Diff Press Sensor: (PSID)
Diff Press Cool Load
diff_press_cool_load_1
8.48872 °F
FALSE
LINK(S): PREV, SYSTEM SETUP, STATUS
COND STATUS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
Cond Water Temp & Pump Status
Cnd H2O In : (F)
CWS In Temp Status
cws_stat_1
67.3 °F
FALSE
/Cnd H2O Out: (F)
CWR Out Status
cwr_stat_1
83.3
FALSE
Cond Flow Status:
Cond Flow SW
cond_flow_1
On
Off, On
FALSE
Cnd Pump#1 Stat:
CW Pump 1 S/S
cw_pump_1_ss_1
Off
Off, On
FALSE
/Cnd Pump#2 Stat:
CW Pump 2 S/S
cw_pump_2_ss_1
Off
Off, On
FALSE
Cond Water Diff Press Sensor: (PSID)
Diff Press Heat Load
diff_press_heat_load_1
8.053761 °F
FALSE
LINK(S): PREV, SYSTEM SETUP, STATUS
MOT VLV OPEN/CLOSE STATUS MENU
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
Module Mot Valve Open/Close Status
Mod1 Mot Valve Open Status:
Module 1 Open
m1_open_5
On
Closed, Open
FALSE
Mod2 Mot Valve Open Status:
Module 2 Open
m2_open_5
On
Closed, Open
FALSE
Mod3 Mot Valve Open Status:
Module 1 Open
m1_open_5
On
Closed, Open
FALSE
Mod4 Mot Valve Open S
Module 4 Open
m4_open_5
Off
Closed, Open
FALSE
Mod5 Mot Valve Open Status:
Module 5 Open
m5_open_5
Off
Closed, Open
FALSE
Mod6 Mot Valve Open Status:
Module 6 Open
m6_open_5
Off
Closed, Open
FALSE
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
MOD X COMP1 DATA
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
M1C1 Suc Pr: (psi)
/ MODULE 1 COMP 1
Module 1 Comp 1 Suction
Pressure
m1_c1_suc_pres_stat_5
40.6
FALSE
Suc SuperHt: (F)
Module 1 Comp 1 Suction
Superheat
m1_c1_suc_superheat_5
8.044445
FALSE
/CH Water In: (F)
CHWR In Temp Status
chwr_stat_1
54.4
FALSE
M1C1 Suc Tp: (F)
Module 1 Comp 1 Suction Temp m1_c1_suct_temp_stat_5
53.6
FALSE
/CH WaterOut: (F)
M1 Evap Leaving Temp
m1_chws_temp_stat_5
51.7
FALSE
M1 VFD VoltIn:
M1 VFD Screw Input
m1vfd_screw_input_1
7.53594 V
0
999
FALSE
/MainTX PIDOUT:
Module 1 Comp 1 Main TXV PID
Out
m1c1_mntx_pid_5
4.1325912
0
999
FALSE
M1C1 Dis Pr: (psi)
Module 1 Comp 1 Disch Press
m1_c1_disch_pres_stat_5
99.3
0
350
FALSE
/M1C1 Dis Tp: (F)
Module 1 Comp 1 Disch Temp
m1_c1_disch_temp_stat_5
110.3
FALSE
M1C1 Status:
/CD Water In : (F)
Module 1 Comp 1 Status
m1_comp1_status_5
On
Off, On
FALSE
M1C1 Fail :
/CD Water Out: (F)
Module 1 Comp 1 Fail
m1_c1_fail_1
Off
Off, On
FALSE
M1C1 Runtime: (h)
Module 1 Comp 1 Runtime
m1_c1_rtime_1
2.3116667
FALSE
/M1C1 Cycles:
Module 1 Comp 1 Cycles
m1_c1_cycles_5
1.0
FALSE
M1C1 Min Runtm:
Module 1 Compr 1 Min Run
m1_c1_min_runtime_5
On
Off, On
FALSE
/M1C1 Min OffTime:
Module 1 Comp 1 Min Off
m1_c1_minimum_off_5
Off
Off, On
FALSE
cdmvPIDOut:
Module 1 Cond Vlv PID Out
m1_cdmv_pidout_5
0.0
0
999
FALSE
%/cdmvVDCScaleOut:
Module 1 Cond Vlv Scaled PID
Out
m1_cdmv_scaled_pidout_5
2.0
0
10
FALSE
CR3 Sol Stat:
Module 1 CR3 valve status
m1_cr3_valve_status_5
Off
Off, On
FALSE
/ CR4 Sol Stat:
Module 1 CR4 valve status
m1_cr4_valve_status_5
On
Off, On
FALSE
NOTE: CR3 is Unload, CR4 is Full Load.
Compressor Amps:
Module 1 Comp 1 Amps
m1c1_amps_stat_5
33.6
0
999
FALSE
Page 2 of 15
10/9/2013
Product Line: UGW
Software Version: UGW-H.08B.13
Chiller Type: COOLING 4 PIPE
LOCAL ACCESS DISPLAY TABLE
/Unit Mode:
Unit Mode
unit_mode_1
Normal Run
Schedule,
NoFlo/Phas,
CHWR High,
CWS Low, Sens
Error,
NoModAvail,
Module Dwn,
Compr Dwn,
NonCritAlm,
Normal Run
FALSE
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
EVAP STATUS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
Evap Water Temp & Pump Status
Evp H2O In: (F)
CHWR In Temp Status
chwr_stat_1
54.4
FALSE
/Evp WaterOut: (F)
CHWS Out Temp Status
chws_stat_1
50.2
FALSE
Evap Flow Status:
Evap Flow SW
evap_flow_1
On
Off, On
FALSE
Ev Pmp#1 Status:
CHW Pump 1 S/S
chw_pump_1_ss_1
Off
Off, On
FALSE
/Ev Pmp#2 Status:
CHW Pump 2 S/S
chw_pump_2_ss_1
Off
Off, On
FALSE
Chil Water Diff Press Sensor: (PSID)
Diff Press Cool Load
diff_press_cool_load_1
8.48872 °F
FALSE
LINK(S): PREV, SYSTEM SETUP, STATUS
COND STATUS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
Cond Water Temp & Pump Status
Cnd H2O In : (F)
CWS In Temp Status
cws_stat_1
67.3 °F
FALSE
/Cnd H2O Out: (F)
CWR Out Status
cwr_stat_1
83.3
FALSE
Cond Flow Status:
Cond Flow SW
cond_flow_1
On
Off, On
FALSE
Cnd Pump#1 Stat:
CW Pump 1 S/S
cw_pump_1_ss_1
Off
Off, On
FALSE
/Cnd Pump#2 Stat:
CW Pump 2 S/S
cw_pump_2_ss_1
Off
Off, On
FALSE
Cond Water Diff Press Sensor: (PSID)
Diff Press Heat Load
diff_press_heat_load_1
8.053761 °F
FALSE
LINK(S): PREV, SYSTEM SETUP, STATUS
MOT VLV OPEN/CLOSE STATUS MENU
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
Module Mot Valve Open/Close Status
Mod1 Mot Valve Open Status:
Module 1 Open
m1_open_5
On
Closed, Open
FALSE
Mod2 Mot Valve Open Status:
Module 2 Open
m2_open_5
On
Closed, Open
FALSE
Mod3 Mot Valve Open Status:
Module 1 Open
m1_open_5
On
Closed, Open
FALSE
Mod4 Mot Valve Open S
Module 4 Open
m4_open_5
Off
Closed, Open
FALSE
Mod5 Mot Valve Open Status:
Module 5 Open
m5_open_5
Off
Closed, Open
FALSE
Mod6 Mot Valve Open Status:
Module 6 Open
m6_open_5
Off
Closed, Open
FALSE
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
MOD X COMP1 DATA
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
M1C1 Suc Pr: (psi)
/ MODULE 1 COMP 1
Module 1 Comp 1 Suction
Pressure
m1_c1_suc_pres_stat_5
40.6
FALSE
Suc SuperHt: (F)
Module 1 Comp 1 Suction
Superheat
m1_c1_suc_superheat_5
8.044445
FALSE
/CH Water In: (F)
CHWR In Temp Status
chwr_stat_1
54.4
FALSE
M1C1 Suc Tp: (F)
Module 1 Comp 1 Suction Temp m1_c1_suct_temp_stat_5
53.6
FALSE
/CH WaterOut: (F)
M1 Evap Leaving Temp
m1_chws_temp_stat_5
51.7
FALSE
M1 VFD VoltIn:
M1 VFD Screw Input
m1vfd_screw_input_1
7.53594 V
0
999
FALSE
/MainTX PIDOUT:
Module 1 Comp 1 Main TXV PID
Out
m1c1_mntx_pid_5
4.1325912
0
999
FALSE
M1C1 Dis Pr: (psi)
Module 1 Comp 1 Disch Press
m1_c1_disch_pres_stat_5
99.3
0
350
FALSE
/M1C1 Dis Tp: (F)
Module 1 Comp 1 Disch Temp
m1_c1_disch_temp_stat_5
110.3
FALSE
M1C1 Status:
/CD Water In : (F)
Module 1 Comp 1 Status
m1_comp1_status_5
On
Off, On
FALSE
M1C1 Fail :
/CD Water Out: (F)
Module 1 Comp 1 Fail
m1_c1_fail_1
Off
Off, On
FALSE
M1C1 Runtime: (h)
Module 1 Comp 1 Runtime
m1_c1_rtime_1
2.3116667
FALSE
/M1C1 Cycles:
Module 1 Comp 1 Cycles
m1_c1_cycles_5
1.0
FALSE
M1C1 Min Runtm:
Module 1 Compr 1 Min Run
m1_c1_min_runtime_5
On
Off, On
FALSE
/M1C1 Min OffTime:
Module 1 Comp 1 Min Off
m1_c1_minimum_off_5
Off
Off, On
FALSE
cdmvPIDOut:
Module 1 Cond Vlv PID Out
m1_cdmv_pidout_5
0.0
0
999
FALSE
%/cdmvVDCScaleOut:
Module 1 Cond Vlv Scaled PID
Out
m1_cdmv_scaled_pidout_5
2.0
0
10
FALSE
CR3 Sol Stat:
Module 1 CR3 valve status
m1_cr3_valve_status_5
Off
Off, On
FALSE
/ CR4 Sol Stat:
Module 1 CR4 valve status
m1_cr4_valve_status_5
On
Off, On
FALSE
NOTE: CR3 is Unload, CR4 is Full Load.
Compressor Amps:
Module 1 Comp 1 Amps
m1c1_amps_stat_5
33.6
0
999
FALSE
Page 1 of 15
10/9/2013
Product Line: UGW
Software Version: UGW-H.08B.13
Chiller Type: COOLING 4 PIPE
STANDBY
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
ClimaCool Corp. CoolLogic
Date:
Time:
CHWS Temp:
EVAP OUT TMP
chws_temp_1
50.1 °F
FALSE
F CWR Temp: (F)
COND OUT TMP
cwr_temp_1
83.3 °F
FALSE
press any key to continue
HOME
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
Chill Water In: (F)
CHWR In Temp Status
chwr_stat_1
54.4
FALSE
/Cool Spt: (F)
Active CHW Setpoint
chw_stp_stat_1
45.0 °F
FALSE
Chill WaterOut: (F)
CHWS Out Temp Status
chws_stat_1
50.2
FALSE
/ Tot Stg Want:
Num of Comp Requested
comp_req_1
2.0
FALSE
Cond Water In : (F)
CWS In Temp Status
cws_stat_1
67.3 °F
FALSE
/ Tot Stg On:
Num of Comp ON
comp_on_1
2.0
FALSE
Cond Water Out: (F)
/ Mode :
Mode
mode_1
CLG
Cooling,
Heating
FALSE
Chil Water Flow :
/Heat Spt: (F)
Evap Flow SW
evap_flow_1
On
No, Yes
FALSE
Cond Water Flo:
Cond Flow SW
cond_flow_1
On
No, Yes
FALSE
/UnitMode:
Unit Mode
unit_mode_1
Normal Run
Schedule, No
Flo/Phas,
CHWR High,
CWS Low, Sens
Error, No
ModAvail,
Module Down,
Compr Down,
NonCrit Alm,
Normal Run
FALSE
LINK(S): STATUS, SYSTEM SETUP, SERVICE MENU SETUP, ALARM
STATUS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Chiller Status Menu
LINK(S): ALL MODULE COMP UNLOAD STATUS,MODULE SIZE STATUS, CHILLER OPER STATUS,EVAP STATUS, COND STATUS,MOT VLV OPEN/CLOSE STATUS MENU,
MOD1 COMP1 DATA,MOD2 COMP1 DATA,MOD3 COMP1 DATA,MOD4 COMP1 DATA,MOD5 COMP1 DATA,MOD6 COMP1 DATA,ALL COMPR RUNTIME STATUS,
ALL COMPR CYCLES STATUS,ALL COMPR SS STATUS, ALL COMPR AMPERAGE STATUS,PREV, CLOCKSET, HOME, ALARM
MODULE SIZE STATUS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value
Editable
Module Size Status Only Legend
Mod1 Size:[
]/ 1= Not Used /4=80Ton Mod
Mod 1 Size
m1_size_st_1
4.0
1
4
FALSE
Mod2 Size:[
]/NOTE:DO NOT SELECT 2 OR 3
Mod 2 Size
m2_size_st_1
4.0
1
4
FALSE
Mod3 Size:[
]
Mod 3 Size
m3_size_st_1
4.0
1
4
FALSE
Mod4 Size:[
]
Mod 4 Size
m4_size_st_1
4.0
1
4
FALSE
Mod5 Size:[
]
Mod 5 Size
m5_size_st_1
1.0
1
4
FALSE
Mod6 Size:[
]
Mod 6 Size
m6_size_st_1
1.0
1
4
FALSE
LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET
CHILLER OPER STATUS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Operating & Loading Status
PID1 Count:
Stage 1 Cooling PID
stg1_clg_pid_1
106.719604
FALSE
/Chil WaterOut: (F)
CHWS Out Temp Status
chws_stat_1
50.2
FALSE
Mod1 VFD Volt:
M1 VFD Screw Input
m1vfd_screw_input_1
7.53594 V
0
999
FALSE
/Mod2 VFD Volt:
M2 VFD Screw Input
m2vfd_screw_input_1
4.4 V
0
999
FALSE
Mod3 VFD Volt:
M3 VFD Screw Input
m3vfd_screw_input_1
0.0 °F
0
999
FALSE
/Mod4 VFD Volt:
M4 VFD Screw Input
m4vfd_screw_input_1
0.0 °F
0
999
FALSE
HPID1 Count:
Stage 1 Heating PID
stg1_htg_pid_1
0.0
FALSE
/Cond WaterOut: (F)
CWR Out Status
cwr_stat_1
83.3
FALSE
Cool Spt:
Active CHW Setpoint
chw_stp_stat_1
45.0 °F
FALSE
F / Heat Spt: (F)
Active Htg Setpoint
cw_stp_stat_1
125.0 °F
FALSE
Unit Stat:
Unit Status
unit_status_1
On
Unit OFF, Unit
ON
FALSE
LOCAL ACCESS DISPLAY TABLE
Page 3 of 15
10/9/2013
Product Line: UGW
Software Version: UGW-H.08B.13
Chiller Type: COOLING 4 PIPE
LOCAL ACCESS DISPLAY TABLE
LINK(S): PREV, STATUS, HOME, ALARM
ALL COMPR RUNTIME STATUS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Compressor Runtime Status
M1C1 Runtm: (h)
Module 1 Comp 1 Runtime
m1_c1_rtime_1
2.3116667
FALSE
/M4C1 Runtm: (h)
Module 4 Comp 1 Runtime
m4_c1_rtime_1
0.015833333
FALSE
M2C1 Runtm: (h)
Module 2 Comp 1 Runtime
m2_c1_rtime_1
3.02
FALSE
/M5C1 Runtm: (h)
Module 5 Comp 1 Runtime
m5_c1_rtime_1
0.0
FALSE
M3C1 Runtm: (h)
Module 3 Comp 1 Runtime
m3_c1_rtime_1
1.773889
FALSE
/M6C1 Runtm: (h)
Module 6 Comp 1 Runtime
m6_c1_rtime_1
0.0
FALSE
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
ALL COMPR CYCLES STATUS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Compressor Cycles Status
M1C1 Cycles:
Module 1 Comp 1 Cycles
m1_c1_cycles_5
1.0
FALSE
/M4C1 Cycles:
Module 4 Comp 1 Cycles
m4_c1_cycles_5
0.0
FALSE
M2C1 Cycles:
Module 2 Comp 1 Cycles
m2_c1_cycles_5
1.0
FALSE
/M5C1 Cycles:
Module 5 Comp 1 Cycles
m5_c1_cycles_5
0.0
FALSE
M3C1 Cycles:
Module 3 Comp 1 Cycles
m3_c1_cycles_5
0.0
FALSE
/M6C1 Cycles:
Module 6 Comp 1 Cycles
m6_c1_cycles_5
0.0
FALSE
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
ALL COMPR SS STATUS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Compressor ON/OFF Status
M1C1 Status:
Module 1 Comp 1 Status
m1_comp1_status_5
On
Off, On
FALSE
/ M4C1 Status:
Module 4 Comp 1 Status
m4_comp1_status_5
Off
Off, On
FALSE
M2C1 Status:
Module 2 Comp 1 Status
m2_comp1_status_5
On
Off, On
FALSE
/ M5C1 Status:
Module 5 Comp 1 Status
m5_comp1_status_5
Off
Off, On
FALSE
M3C1 Status:
Module 3 Comp 1 Status
m3_comp1_status_5
Off
Off, On
FALSE
/ M6C1 Status:
Module 6 Comp 1 Status
m6_comp1_status_5
Off
Off, On
FALSE
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
ALL COMPR AMPERAGE STATUS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Compressor Amperage Status
M1C1 Compr Amps:
Module 1 Comp 1 Amps
m1c1_amps_stat_5
33.6
FALSE
/M4C1 Compr Amps:
Module 4 Comp 1 Amps
m4c1_amps_stat_5
0.4
FALSE
M2C1 Compr Amps:
Module 2 Comp 1 Amps
m2c1_amps_stat_5
25.4
FALSE
/M5C1 Compr Amps:
Module 5 Comp 1 Amps
m5c1_amps_stat_5
0.0
FALSE
M3C1 Compr Amps:
Module 3 Comp 1 Amps
m3c1_amps_stat_5
0.4
FALSE
/M6C1 Compr Amps:
Module 6 Comp 1 Amps
m6c1_amps_stat_5
0.0
FALSE
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
SYSTEM SETUP FN2
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic System Setup FN2
LINK(S): GENERAL SYS SETTINGS,HEAT & COOL SETPOINT MENUS,EVAP PUMP SETUP,COND PUMP SETUP,LEAD COMPR ROTATION SETUP,ALARM LOCKOUT RESET,SCHEDULES,
PREV, STATUS, HOME, ALARM
GENERAL SYS SETTINGS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value
Editable
CoolLogic General System Settings FN4
Chiller Control Type
Control Type
control_type_1
Cool Control
Cool Cntrl,
Heat Cntrl,
Heat Rcvry
TRUE
Chiller Control Source
Control Source
control_source_1
Digital Input
Dig Input,
Keypad, BAS
TRUE
Enable Chiller from Keypad?
Unit Enable (keypad)
enable_keypad_1
On
Off, On
TRUE
Mod Ref Type
Module Compr Ref Type
mod_comp_ref_type_5
134a
22, 407C,
410a, 134a
TRUE
Chiller Model Type:
Chiller Model Type
chiller_model_type_5
UGW
UGW, UGH,
UGR
TRUE
Cool Design Delta Temp
FULL LD COOL DES TD
cool_design_dt_1
-10.0
-50
50
TRUE
Heat Design Delta Temp
FULL LD HEAT DES TD
heat_design_dt_1
10.0
-50
50
TRUE
Use High Amb Tmp Limit?
HI AMBIENT TMP LIM
hi_amb_tmp_lim_1
No
No, Yes
TRUE
Software Version: UGW-H.08b.13
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
HEAT & COOL SETPOINT MENUS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Heat and Cool Setpoints