Control access display table, Local access display table – ClimaCool UGW Manual User Manual
Page 41

39
www.climacoolcorp.com
Control Access Display Table
Page 11 of 15
10/9/2013
Product Line: UGW
Software Version: UGW-H.08B.13
Chiller Type: COOLING 4 PIPE
LOCAL ACCESS DISPLAY TABLE
Fix Module #5 as Open Module?:
Fix Mod5 as Open
fix_module5_open_1
No
No, Yes
TRUE
Never Close Module #5?:
Never Close Module #5
never_close_mod5_1
No
No, Yes
TRUE
Fix Module #6 as Open Module?:
Fix Mod6 as Open
fix_module6_open_1
No
No, Yes
TRUE
Never Close Module #6?:
Never Close Module #6
never_close_mod6_1
No
No, Yes
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
MOTORIZED VALVE OPTION
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Motorized Valve Option
Motorized Valves:
Motorized Valve Options
mot_vlv_opt_5
MVCONDEVA
P
No Mot Vlvs,
Evap Mot Vlvs
Only,
Cond&Evap
Mot Vlvs
TRUE
Cond Mot Vlv Delay Before Alarm:
Module COND VLV ALM DELAY mod_cond_vlv_alm_delay_5
600.0
1
999
TRUE
Evap Mot Vlv Delay Before Alarm:
Module EVAP VLV ALM DELAY
mod_evap_vlv_alm_delay_5
600.0
1
999
TRUE
Low Head Press Setpoint Status:
Module Lo Disch Press Setpt
mod_lo_disch_press_sp_5
100.0
1
585
FALSE
Low Head Press Setpoint R410A :
Low Head Press Sp 410a
mod_lo_disch_press_sp_410_5
220.0
1
650
TRUE
Low Head Press Setpoint R134a :
Low Head Press Sp 134a
mod_lo_disch_press_sp_134_5
100.0
1
450
TRUE
Low Head Press Setpoint R407C :
Low Head Press Sp 407
mod_lo_disch_press_sp_407_5
150.0
1
450
TRUE
Cond Mot Vlv PID Settings
Cond MV PID Interval:
CDMV PID Interval
cdmv_interval_5
2.0 sec
1
180
TRUE
Cond MV PID P-Gain :
CDMV PID P-gain
cdmv_p_gain_5
8.0
1
999
TRUE
Cond MV PID I-Gain :
CDMV PID I-gain
cdmv_i_gain_5
0.02
0
99
TRUE
Cond MV PID Deadband:
CDMV PID Deadband
cdmv_pid_db_5
0.0
0
99
TRUE
Cond MV PID Ramp sec:
CDMV PID RAMP
cdmv_pid_ramp_5
2.0
1
999
TRUE
Cond MV PID Min % :
CDMV PID Minimum Percent
cdmv_pid_mnpct_5
20.0
0
100
TRUE
Module Min CDMV ADJ :
Mod CDMV PID Minimum VDC
mod_min_cdmv_adj_5
3.4
0
100
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
MOT VLV SIGNAL TO CLOSE MENU
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
Module Mot Valve Signal to Close
Mod1 Mot Valve Signal to Close:
Module 1 Closed
m1_closed_5
Off
No, Yes
FALSE
Mod2 Mot Valve Signal to Close:
Module 2 Closed
m2_closed_5
Off
No, Yes
FALSE
Mod3 Mot Valve Signal to Close:
Module 3 Closed
m3_closed_5
On
No, Yes
FALSE
Mod4 Mot Valve Signal to Close:
Module 4 Closed
m4_closed_5
On
No, Yes
FALSE
Mod5 Mot Valve Signal to Close:
Module 5 Closed
m5_closed_5
Off
No, Yes
FALSE
Mod6 Mot Valve Signal to Close:
Module 6 Closed
m6_closed_5
Off
No, Yes
FALSE
Delay Before Closing Mot Valves:
Delay Before Closing Mot Vlv
close_vlv_delay_5
25.0
1
999
TRUE
Open Ext Bypass if NO Comps ON?
Open Bypass Valves by NO
Comps ON
open_byp_vlv_on_no_cmps_1
Off
No, Yes
TRUE
Cool Header Bypass Vlv Status:
Cool Header Ext Bypass Valve
cl_hdr_ext_byp_vlv_1
Off
Closed, Open
FALSE
Heat Header Bypass Vlv Status:
Heat Header Ext Bypass Valve
ht_hdr_ext_byp_vlv_1
Off
Closed, Open
FALSE
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
MASTER INPUT CHNLS 6, &10 SETUP
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value
Editable
Master Controller Inputs 6 & 10 Setup
Input Chn#10Type:
Input Chnl 10 Type
inp_10_point_type_1
NONE
None, Remote
Heat Trg
TRUE
Min Cond Wat Out Setpt: (F)
MIN HEAT TRG LIM
min_cw_temp_stp_1
75.0 °F
60
165
TRUE
Max Cond Wat Out Setpt: (F)
MAX HEAT TRG LIM
max_cw_temp_stp_1
135.0 °F
60
165
TRUE
Input Chn#10Scaling:
AI10 Type Rem Ht Trg
an_inp10_typ_1
NONE
NONE, 4-20
ma, 2-10VDC
TRUE
Input Chn#6 Type:
Input Chnl 6 Type
inp_6_point_type_1
NONE
None, Remote
Cool Trg
TRUE
Min Evap Wat Out Setpt: (F)
MIN COOL TRG LIM
min_chw_temp_stp_1
40.0 °F
0
75
TRUE
Max Evap Wat Out Setpt: (F)
MAX COOL TRG LIM
max_chw_temp_stp_1
62.0 °F
0
75
TRUE
Input Chn#6 Scaling:
AI6 Type Off is 0-10
an_inp6_typ_1
NONE
NONE, 4-20
ma, 2-10VDC
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME
MASTER INPUT CHNL 7 DEM LIMIT SETUP
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
Master Control Demand Limiting Chnl#7
COOL & HEAT MODE DEMAND LIMITING
Input Chn#7 Type:
Input Chnl 7 Type
inp_7_point_type_1
None
None, Demand
Lim TrgRst,
Demand Lim
Max #Cmp
TRUE
Max Neg Cool Out Trg Reset: (F)
MAX NEG DEM LIM COOL RESET max_neg_chw_stp_reset_1
0.0 °F
0
100
TRUE
Max Pos Cool Out Trg Reset: (F)
MAX POS DEM LIM COOL RESET max_pos_chw_stp_reset_1
10.0 °F
0
100
TRUE
Max Neg Heat Out Trg Reset: (F)
MAX NEG DEM LIM HEAT RESET max_neg_cw_stp_reset_1
0.0 °F
0
100
TRUE
Max Pos Heat Out Trg Reset: (F)
MAX POS DEM LIM HEAT RESET max_pos_cw_stp_reset_1
10.0 °F
0
100
TRUE
Page 12 of 15
10/9/2013
Product Line: UGW
Software Version: UGW-H.08B.13
Chiller Type: COOLING 4 PIPE
LOCAL ACCESS DISPLAY TABLE
Input Chn#7 Scaling:
AI7 Type Rem Cl Trg or Dem Lim an_inp7_typ_1
NONE
NONE, 4-20
ma, 2-10VDC
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME
MASTER INPUT 8 & 11 SETUP
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
Channels 8,11&1-13 Setup(Wtr Diff Pres)
Use Dif Pr. Sens for Chn8,11&1-13?
Use Diff Press Flow Sensors
use_diff_pr_flow_sens_1
Yes
No, Yes
TRUE
*Std CC Dif Pres Sensor Range=0-43 psid
Min&Max Scale Range-Cold Wtr Dif Pr.:
Cold Wtr Chn#08 Scaling Type:
AI8 Type
an_inp8_typ_1
0-5VDC
4-20 ma, 0-
10VDC, 0-5
VDC
TRUE
Cold Wtr Min Scale @ 0V or 0mA :
Min Cool Diff Press Scale @ 0
min_scale_cool_diff_pr_1
-5.43
-99.9
999.9
TRUE
Cold Wtr Max Scale@5V,10Vor20mA:
Max Cool Diff Press Scale
max_scale_cool_diff_pr_1
48.94
-99.9
999.9
TRUE
Min&Max Scale Range-Hot Wtr Dif Pr.:
Hot Wtr Chn #11 Scaling Type:
AI11 Type
an_inp11_typ_1
0-5VDC
4-20 ma, 0-
10VDC, 0-5
VDC
TRUE
Hot Wtr Min Scale @ 0V or 0mA :
Min Source Diff Press Scale @ 0 min_scale_heat_diff_pr_1
-5.43
-99.9
999.9
TRUE
Hot Wtr Max Scale@5V,10Vor20mA:
Max Source Diff Press Scale
max_scale_heat_diff_pr_1
48.94
-99.9
999.9
TRUE
Cond Wat Min Dif Pr Flo Setpt: (PSI)
LO CW Diff Press
lo_cw_diff_pr_1
2.0
0
46
TRUE
Chil Wat Min Dif Pr Flo Setpt: (PSI)
Lo CHW Diff Pressure
lo_chw_diff_pr_1
2.0
0
46
TRUE
Differential Pressure Sensure Readings:
Cond Water Diff Press Sensor: (PSID)
Diff Press Heat Load
diff_press_heat_load_1
8.053761 °F
FALSE
Chil Water Diff Press Sensor: (PSID)
Diff Press Cool Load
diff_press_cool_load_1
8.48872 °F
FALSE
LINK(S): PREV, SYSTEM SETUP, HOME
WATER MAINS & AIR TEMP LIMITS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value
Editable
Main Hdr Water & Air Temp Alarm Limits
Evap Wat In Lo Limit: (F)
CHWR Enable Lo Limit
chwr_lo_lim_1
38.0
0
165 TRUE
Evap Wat In Hi Limit: (F)
CHWR Enable Hi Limit
chwr_hi_lim_1
90.0
0
165 TRUE
Evap Wat Out Lo Limit: (F)
LO EVAP LVG TMP
chws_low_lim_1
38.0
0
165 TRUE
Evap Wat Out Hi Limit: (F)
HI EVAP LVG TMP
chws_hi_lim_1
90.0
0
165 TRUE
Cond Wat In Lo Limit: (F)
LO CND LVG TMP
cws_low_lim_1
55.0
10
165 TRUE
Cond Wat Out Lo Limit: (F)
CWR Enable Lo Limit
cwr_lo_lim_1
55.0
10
165 TRUE
Main Header Cond Water Hi Limit:
CWR Cond Wtr Out UGW Hi Limit: (F)
HI COND LVG TMP UCW
ucw_cwr_hi_lim_1
118.0
10
165
TRUE
CWS Cond Wtr In UGW Hi Limit: (F)
HI COND ENT TMP UCW
ucw_cws_hi_lim_1
114.0
10
165
TRUE
CWR Cond Wtr Out UGH Hi Limit: (F)
HI COND LVG TMP UCH
uch_cwr_hi_lim_1
135.0
10
165
TRUE
CWS Cond Wtr In UGH Hi Limit: (F)
HI COND ENT TMP UCH
uch_cws_hi_lim_1
135.0
10
165
TRUE
Cond Wat In Hi Limit: (F)
Module Entering Cond Water
Temp Setpoint
cws_hi_lim_1
114.0
10
165
FALSE
Cond Wat Out Hi Limit: (F)
Module Leaving Cond Water
Temp Setpoint
cwr_hi_lim_1
118.0
10
165
FALSE
Use Hi Amb Temp Limit?
HI AMBIENT TMP LIM
hi_amb_tmp_lim_1
No
No, Yes
TRUE
Outdoor Air Lo Limit: (F)
LO AMBIENT TMP
lo_ambient_tmp_1
45.0 °F
-20
140
TRUE
Outdoor Air Hi Limit: (F)
HI AMBIENT TMP
hi_ambient_tmp_1
110.0 °F
-20
140
TRUE
Allow Evap Wtr Pump Menu Access?:
Use CHW Pump Menu
use_chw_pump_menu_1
No
No, Yes
TRUE
Allow Cond Wtr Pump Menu Access?:
Use CW Pump Menu
use_cw_pump_menu_1
No
No, Yes
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME
STARTUP & STAGE DELAYS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value
Editable
Start-Up,Stage-Up & Stage-Dn Delays
Start-Up Time Delay (sec)
Start-Up Delay
o562_1
45.0 sec
1
999
TRUE
Stage-Up Delay (sec)
Stage Up Delay
n003_1
45.0 sec
1
999
TRUE
Stage-Down Delay (sec)
Stage Down Delay
n006_1
45.0 sec
1
999
TRUE
Mode Change Delay (sec)
Mode Change Delay
mode_change_delay_1
30.0 sec
1
3000
TRUE
LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET
AUTO HEAT TRG RESET ON OAT
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Heat Tgr Reset on OAT
Auto Heat Trg Reset :
OA AUTO HT TRG ON/OFF
auto_ht_trg_onof_1
0.0
Off, On
TRUE
Max OAT for Scaling Cond Trg: (F)
MAX OAT FOR HTG TRG RES
max_oat_htg_trg_reset_1
60.0 °F
0
140
TRUE
Min OAT for Scaling Cond Trg: (F)
MIN OAT FOR HTG TRG RESET
min_oat_htg_trg_reset_1
0.0 °F
-20
140
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME
COMPR SEQUENCING METHOD
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Compr Sequencing Method
Compr Equal Runtime:
Equal Runtime
equal_rtim_1
On
Off, On
TRUE
Page 12 of 15
10/9/2013
Product Line: UGW
Software Version: UGW-H.08B.13
Chiller Type: COOLING 4 PIPE
LOCAL ACCESS DISPLAY TABLE
Input Chn#7 Scaling:
AI7 Type Rem Cl Trg or Dem Lim an_inp7_typ_1
NONE
NONE, 4-20
ma, 2-10VDC
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME
MASTER INPUT 8 & 11 SETUP
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
Channels 8,11&1-13 Setup(Wtr Diff Pres)
Use Dif Pr. Sens for Chn8,11&1-13?
Use Diff Press Flow Sensors
use_diff_pr_flow_sens_1
Yes
No, Yes
TRUE
*Std CC Dif Pres Sensor Range=0-43 psid
Min&Max Scale Range-Cold Wtr Dif Pr.:
Cold Wtr Chn#08 Scaling Type:
AI8 Type
an_inp8_typ_1
0-5VDC
4-20 ma, 0-
10VDC, 0-5
VDC
TRUE
Cold Wtr Min Scale @ 0V or 0mA :
Min Cool Diff Press Scale @ 0
min_scale_cool_diff_pr_1
-5.43
-99.9
999.9
TRUE
Cold Wtr Max Scale@5V,10Vor20mA:
Max Cool Diff Press Scale
max_scale_cool_diff_pr_1
48.94
-99.9
999.9
TRUE
Min&Max Scale Range-Hot Wtr Dif Pr.:
Hot Wtr Chn #11 Scaling Type:
AI11 Type
an_inp11_typ_1
0-5VDC
4-20 ma, 0-
10VDC, 0-5
VDC
TRUE
Hot Wtr Min Scale @ 0V or 0mA :
Min Source Diff Press Scale @ 0 min_scale_heat_diff_pr_1
-5.43
-99.9
999.9
TRUE
Hot Wtr Max Scale@5V,10Vor20mA:
Max Source Diff Press Scale
max_scale_heat_diff_pr_1
48.94
-99.9
999.9
TRUE
Cond Wat Min Dif Pr Flo Setpt: (PSI)
LO CW Diff Press
lo_cw_diff_pr_1
2.0
0
46
TRUE
Chil Wat Min Dif Pr Flo Setpt: (PSI)
Lo CHW Diff Pressure
lo_chw_diff_pr_1
2.0
0
46
TRUE
Differential Pressure Sensure Readings:
Cond Water Diff Press Sensor: (PSID)
Diff Press Heat Load
diff_press_heat_load_1
8.053761 °F
FALSE
Chil Water Diff Press Sensor: (PSID)
Diff Press Cool Load
diff_press_cool_load_1
8.48872 °F
FALSE
LINK(S): PREV, SYSTEM SETUP, HOME
WATER MAINS & AIR TEMP LIMITS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value
Editable
Main Hdr Water & Air Temp Alarm Limits
Evap Wat In Lo Limit: (F)
CHWR Enable Lo Limit
chwr_lo_lim_1
38.0
0
165 TRUE
Evap Wat In Hi Limit: (F)
CHWR Enable Hi Limit
chwr_hi_lim_1
90.0
0
165 TRUE
Evap Wat Out Lo Limit: (F)
LO EVAP LVG TMP
chws_low_lim_1
38.0
0
165 TRUE
Evap Wat Out Hi Limit: (F)
HI EVAP LVG TMP
chws_hi_lim_1
90.0
0
165 TRUE
Cond Wat In Lo Limit: (F)
LO CND LVG TMP
cws_low_lim_1
55.0
10
165 TRUE
Cond Wat Out Lo Limit: (F)
CWR Enable Lo Limit
cwr_lo_lim_1
55.0
10
165 TRUE
Main Header Cond Water Hi Limit:
CWR Cond Wtr Out UGW Hi Limit: (F)
HI COND LVG TMP UCW
ucw_cwr_hi_lim_1
118.0
10
165
TRUE
CWS Cond Wtr In UGW Hi Limit: (F)
HI COND ENT TMP UCW
ucw_cws_hi_lim_1
114.0
10
165
TRUE
CWR Cond Wtr Out UGH Hi Limit: (F)
HI COND LVG TMP UCH
uch_cwr_hi_lim_1
135.0
10
165
TRUE
CWS Cond Wtr In UGH Hi Limit: (F)
HI COND ENT TMP UCH
uch_cws_hi_lim_1
135.0
10
165
TRUE
Cond Wat In Hi Limit: (F)
Module Entering Cond Water
Temp Setpoint
cws_hi_lim_1
114.0
10
165
FALSE
Cond Wat Out Hi Limit: (F)
Module Leaving Cond Water
Temp Setpoint
cwr_hi_lim_1
118.0
10
165
FALSE
Use Hi Amb Temp Limit?
HI AMBIENT TMP LIM
hi_amb_tmp_lim_1
No
No, Yes
TRUE
Outdoor Air Lo Limit: (F)
LO AMBIENT TMP
lo_ambient_tmp_1
45.0 °F
-20
140
TRUE
Outdoor Air Hi Limit: (F)
HI AMBIENT TMP
hi_ambient_tmp_1
110.0 °F
-20
140
TRUE
Allow Evap Wtr Pump Menu Access?:
Use CHW Pump Menu
use_chw_pump_menu_1
No
No, Yes
TRUE
Allow Cond Wtr Pump Menu Access?:
Use CW Pump Menu
use_cw_pump_menu_1
No
No, Yes
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME
STARTUP & STAGE DELAYS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value
Editable
Start-Up,Stage-Up & Stage-Dn Delays
Start-Up Time Delay (sec)
Start-Up Delay
o562_1
45.0 sec
1
999
TRUE
Stage-Up Delay (sec)
Stage Up Delay
n003_1
45.0 sec
1
999
TRUE
Stage-Down Delay (sec)
Stage Down Delay
n006_1
45.0 sec
1
999
TRUE
Mode Change Delay (sec)
Mode Change Delay
mode_change_delay_1
30.0 sec
1
3000
TRUE
LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET
AUTO HEAT TRG RESET ON OAT
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Heat Tgr Reset on OAT
Auto Heat Trg Reset :
OA AUTO HT TRG ON/OFF
auto_ht_trg_onof_1
0.0
Off, On
TRUE
Max OAT for Scaling Cond Trg: (F)
MAX OAT FOR HTG TRG RES
max_oat_htg_trg_reset_1
60.0 °F
0
140
TRUE
Min OAT for Scaling Cond Trg: (F)
MIN OAT FOR HTG TRG RESET
min_oat_htg_trg_reset_1
0.0 °F
-20
140
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME
COMPR SEQUENCING METHOD
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Compr Sequencing Method
Compr Equal Runtime:
Equal Runtime
equal_rtim_1
On
Off, On
TRUE
Page 12 of 15
10/9/2013
Product Line: UGW
Software Version: UGW-H.08B.13
Chiller Type: COOLING 4 PIPE
LOCAL ACCESS DISPLAY TABLE
Input Chn#7 Scaling:
AI7 Type Rem Cl Trg or Dem Lim an_inp7_typ_1
NONE
NONE, 4-20
ma, 2-10VDC
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME
MASTER INPUT 8 & 11 SETUP
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
Channels 8,11&1-13 Setup(Wtr Diff Pres)
Use Dif Pr. Sens for Chn8,11&1-13?
Use Diff Press Flow Sensors
use_diff_pr_flow_sens_1
Yes
No, Yes
TRUE
*Std CC Dif Pres Sensor Range=0-43 psid
Min&Max Scale Range-Cold Wtr Dif Pr.:
Cold Wtr Chn#08 Scaling Type:
AI8 Type
an_inp8_typ_1
0-5VDC
4-20 ma, 0-
10VDC, 0-5
VDC
TRUE
Cold Wtr Min Scale @ 0V or 0mA :
Min Cool Diff Press Scale @ 0
min_scale_cool_diff_pr_1
-5.43
-99.9
999.9
TRUE
Cold Wtr Max Scale@5V,10Vor20mA:
Max Cool Diff Press Scale
max_scale_cool_diff_pr_1
48.94
-99.9
999.9
TRUE
Min&Max Scale Range-Hot Wtr Dif Pr.:
Hot Wtr Chn #11 Scaling Type:
AI11 Type
an_inp11_typ_1
0-5VDC
4-20 ma, 0-
10VDC, 0-5
VDC
TRUE
Hot Wtr Min Scale @ 0V or 0mA :
Min Source Diff Press Scale @ 0 min_scale_heat_diff_pr_1
-5.43
-99.9
999.9
TRUE
Hot Wtr Max Scale@5V,10Vor20mA:
Max Source Diff Press Scale
max_scale_heat_diff_pr_1
48.94
-99.9
999.9
TRUE
Cond Wat Min Dif Pr Flo Setpt: (PSI)
LO CW Diff Press
lo_cw_diff_pr_1
2.0
0
46
TRUE
Chil Wat Min Dif Pr Flo Setpt: (PSI)
Lo CHW Diff Pressure
lo_chw_diff_pr_1
2.0
0
46
TRUE
Differential Pressure Sensure Readings:
Cond Water Diff Press Sensor: (PSID)
Diff Press Heat Load
diff_press_heat_load_1
8.053761 °F
FALSE
Chil Water Diff Press Sensor: (PSID)
Diff Press Cool Load
diff_press_cool_load_1
8.48872 °F
FALSE
LINK(S): PREV, SYSTEM SETUP, HOME
WATER MAINS & AIR TEMP LIMITS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value
Editable
Main Hdr Water & Air Temp Alarm Limits
Evap Wat In Lo Limit: (F)
CHWR Enable Lo Limit
chwr_lo_lim_1
38.0
0
165 TRUE
Evap Wat In Hi Limit: (F)
CHWR Enable Hi Limit
chwr_hi_lim_1
90.0
0
165 TRUE
Evap Wat Out Lo Limit: (F)
LO EVAP LVG TMP
chws_low_lim_1
38.0
0
165 TRUE
Evap Wat Out Hi Limit: (F)
HI EVAP LVG TMP
chws_hi_lim_1
90.0
0
165 TRUE
Cond Wat In Lo Limit: (F)
LO CND LVG TMP
cws_low_lim_1
55.0
10
165 TRUE
Cond Wat Out Lo Limit: (F)
CWR Enable Lo Limit
cwr_lo_lim_1
55.0
10
165 TRUE
Main Header Cond Water Hi Limit:
CWR Cond Wtr Out UGW Hi Limit: (F)
HI COND LVG TMP UCW
ucw_cwr_hi_lim_1
118.0
10
165
TRUE
CWS Cond Wtr In UGW Hi Limit: (F)
HI COND ENT TMP UCW
ucw_cws_hi_lim_1
114.0
10
165
TRUE
CWR Cond Wtr Out UGH Hi Limit: (F)
HI COND LVG TMP UCH
uch_cwr_hi_lim_1
135.0
10
165
TRUE
CWS Cond Wtr In UGH Hi Limit: (F)
HI COND ENT TMP UCH
uch_cws_hi_lim_1
135.0
10
165
TRUE
Cond Wat In Hi Limit: (F)
Module Entering Cond Water
Temp Setpoint
cws_hi_lim_1
114.0
10
165
FALSE
Cond Wat Out Hi Limit: (F)
Module Leaving Cond Water
Temp Setpoint
cwr_hi_lim_1
118.0
10
165
FALSE
Use Hi Amb Temp Limit?
HI AMBIENT TMP LIM
hi_amb_tmp_lim_1
No
No, Yes
TRUE
Outdoor Air Lo Limit: (F)
LO AMBIENT TMP
lo_ambient_tmp_1
45.0 °F
-20
140
TRUE
Outdoor Air Hi Limit: (F)
HI AMBIENT TMP
hi_ambient_tmp_1
110.0 °F
-20
140
TRUE
Allow Evap Wtr Pump Menu Access?:
Use CHW Pump Menu
use_chw_pump_menu_1
No
No, Yes
TRUE
Allow Cond Wtr Pump Menu Access?:
Use CW Pump Menu
use_cw_pump_menu_1
No
No, Yes
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME
STARTUP & STAGE DELAYS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value
Editable
Start-Up,Stage-Up & Stage-Dn Delays
Start-Up Time Delay (sec)
Start-Up Delay
o562_1
45.0 sec
1
999
TRUE
Stage-Up Delay (sec)
Stage Up Delay
n003_1
45.0 sec
1
999
TRUE
Stage-Down Delay (sec)
Stage Down Delay
n006_1
45.0 sec
1
999
TRUE
Mode Change Delay (sec)
Mode Change Delay
mode_change_delay_1
30.0 sec
1
3000
TRUE
LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET
AUTO HEAT TRG RESET ON OAT
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Heat Tgr Reset on OAT
Auto Heat Trg Reset :
OA AUTO HT TRG ON/OFF
auto_ht_trg_onof_1
0.0
Off, On
TRUE
Max OAT for Scaling Cond Trg: (F)
MAX OAT FOR HTG TRG RES
max_oat_htg_trg_reset_1
60.0 °F
0
140
TRUE
Min OAT for Scaling Cond Trg: (F)
MIN OAT FOR HTG TRG RESET
min_oat_htg_trg_reset_1
0.0 °F
-20
140
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME
COMPR SEQUENCING METHOD
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Compr Sequencing Method
Compr Equal Runtime:
Equal Runtime
equal_rtim_1
On
Off, On
TRUE
Page 13 of 15
10/9/2013
Product Line: UGW
Software Version: UGW-H.08B.13
Chiller Type: COOLING 4 PIPE
LOCAL ACCESS DISPLAY TABLE
SWAP COMP LEAD :
Manually Refresh Lead Module man_refr_modlead_1
Do Not
Refresh Lead
Do Not Refresh
Lead, Refresh
Lead
TRUE
LINK(S): LEAD COMPR ROTATION SETUP,PREV, SYSTEM SETUP, HOME, ALARM
HEAT BIN LOAD CAP% STATUS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Heat BinLoad Cap% Status
HeatBin 10% (h)
HEAT BIN 0-10 % HRS
heat_bin_0010_1
0.0
FALSE
/ HeatBin 60% (h)
HEAT BIN 50-60 % HRS
heat_bin_5060_1
0.0
FALSE
HeatBin 20% (h)
HEAT BIN 10-20 % HRS
heat_bin_1020_1
0.0
FALSE
/ HeatBin 70% (h)
HEAT BIN 60-70 % HRS
heat_bin_6070_1
0.0
FALSE
HeatBin 30% (h)
HEAT BIN 20-30 % HRS
heat_bin_2030_1
0.0
FALSE
/ HeatBin 80% (h)
HEAT BIN 70-80 % HRS
heat_bin_7080_1
0.0
FALSE
HeatBin 40% (h)
HEAT BIN 30-40 % HRS
heat_bin_3040_1
0.0
FALSE
/ HeatBin 90% (h)
HEAT BIN 80-90 % HRS
heat_bin_8090_1
0.0
FALSE
HeatBin 50% (h)
HEAT BIN 40-50 % HRS
heat_bin_4050_1
0.0
FALSE
/HeatBin 100% (h)
HEAT BIN 90-100 % HRS
heat_bin_90100_1
0.0
FALSE
Reset Hours in ALL Heat Bins:
HEAT BIN RESET
heat_bin_reset_1
Off
Off, On
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
COOL BIN LOAD CAP% STATUS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value
Editable
CoolLogic Cool BinLoad Cap% Status
CoolBin 10% (h)
COOL BIN 0-10 % HRS
cool_bin_0010_1
0.044166666
FALSE
/ CoolBin 60% (h)
COOL BIN 50-60 % HRS
cool_bin_5060_1
0.0
FALSE
CoolBin 20% (h)
COOL BIN 10-20 % HRS
cool_bin_1020_1
0.11083333
FALSE
/ CoolBin 70% (h)
COOL BIN 60-70 % HRS
cool_bin_6070_1
0.0
FALSE
CoolBin 30% (h)
COOL BIN 20-30 % HRS
cool_bin_2030_1
0.11305556
FALSE
/ CoolBin 80% (h)
COOL BIN 70-80 % HRS
cool_bin_7080_1
0.0
FALSE
CoolBin 40% (h)
COOL BIN 30-40 % HRS
cool_bin_3040_1
0.03
FALSE
/ CoolBin 90% (h)
COOL BIN 80-90 % HRS
cool_bin_8090_1
0.0
FALSE
CoolBin 50% (h)
COOL BIN 40-50 % HRS
cool_bin_4050_1
0.0
FALSE
/CoolBin 100% (h)
COOL BIN 90-100 % HRS
cool_bin_90100_1
0.0
FALSE
Reset Hours in ALL Cool Bins:
COOL BIN RESET
cool_bin_reset_1
Off
Off, On
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
MAIN TXV PID SETTINGS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
MAIN TXV PID Settings
M1C1 MainTXV PID Output: (%)
Module 1 Comp 1 Main TXV PID
Out
m1c1_mntx_pid_5
4.1325912
FALSE
M2C1 MainTXV PID Output: (%)
Module 2 Comp 1 Main TXV PID
Out
m2c1_mntx_pid_5
3.0173447
FALSE
M3C1 MainTXV PID Output: (%)
Module 3 Comp 1 Main TXV PID
Out
m3c1_mntx_pid_5
0.0
FALSE
M4C1 MainTXV PID Output: (%)
Module 4 Comp 1 Main TXV PID
Out
m4c1_mntx_pid_5
0.0
FALSE
Main TXV Superheat Setpoint:
Main TX SPRHT Setpoint
mntx_sprht_stpt_5
8.0
0
99
TRUE
Main TXV PID Interval:
MNTX PID Interval
mntx_interval_5
3.0 sec
1
999
TRUE
Main TXV PID Gain :
MNTX PID gain
mntx_gain_5
1.0
0
999
TRUE
Main TXV PID P-Gain :
MNTX PID P-gain
mntx_p_gain_5
11.0
0
999
TRUE
Main TXV PID I-Gain#1:
MNTX PID I-gain
mntx_i_gain_5
0.8
0
99
TRUE
Main TXV PID I-Gain#2:
MNTX PID IG2
mntx_i_gain2_5
0.0
0
99
TRUE
Main TXV PID D-Gain#1:
MNTX PID D-gain
mntx_d_gain_5
0.0
0
99
TRUE
Main TXV PID Rise : (%/min)
MNTX PID Rise
mntx_pid_rise_5
30.0 sec
1
999
TRUE
Main TXV PID Fall : (%/min)
MNTX PID Fall
mntx_pid_fall_5
30.0
1
999
TRUE
Main TXV PID Limit : (%)
Main TX Maximum PID
mntx_max_pid_5
65.0
55
999
FALSE
Main TXV PID Deadbd1 :
mntx_db1_5
0
99
TRUE
Main TXV PID Deadbd2 :
MNTX PID DB2
mntx_pid_db2_5
0.0
0
99
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
MAIN TXV PSI PID SETTINGS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
MAIN TXV PID Settings FOR PSI
M1C1 MainTXV PID Output : (%)
Module 1 Comp 1 Main TXV PID
Out
m1c1_mntx_pid_5
4.1325912
FALSE
M2C1 MainTXV PID Output : (%)
Module 2 Comp 1 Main TXV PID
Out
m2c1_mntx_pid_5
3.0173447
FALSE
M3C1 MainTXV PID Output : (%)
Module 3 Comp 1 Main TXV PID
Out
m3c1_mntx_pid_5
0.0
FALSE
M4C1 MainTXV PID Output : (%)
Module 4 Comp 1 Main TXV PID
Out
m4c1_mntx_pid_5
0.0
FALSE
MainTXV for PSI PID Interval:
MNTX PID PSI Interval
mntx_psi_interval_5
3.0 sec
1
999
TRUE