Control Access Display Table
Page 9 of 15
10/9/2013
Product Line: UGW
Software Version: UGW-H.08B.13
Chiller Type: COOLING 4 PIPE
LOCAL ACCESS DISPLAY TABLE
/C1SucPr: (ps)
Module 1 Comp 1 Suction
Pressure
m1_c1_suc_pres_stat_5
40.6
FALSE
C1DisTmpCal: (F)
M1C1 DIS Temp Calib. Point
m1c1_disch_temp_cp_5
0.0
-250
250
TRUE
/C1DisTp: (F)
Module 1 Comp 1 Disch Temp
m1_c1_disch_temp_stat_5
110.3
FALSE
C1SucTempCal: (F)
M1C1 SUC Temp Calib. Point
m1c1_suc_tmp_cp_5
0.0
-250
250
TRUE
/C1SucTp: (F)
Module 1 Comp 1 Suction Temp m1_c1_suct_temp_stat_5
53.6
FALSE
C1CompAmpCal:
M1C1 Amps Calib. Point
m1c1_amps_cp_5
3.0
-250
250
TRUE
/C1 Amps:
Module 1 Comp 1 Amps
m1c1_amps_stat_5
33.6
FALSE
LINK(S): PREV, SYSTEM SETUP, HOME
LOCK WATER TEMPS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value
Editable
Lock Main Header Water & Air Temps
Evap Wat In Lock :
Lock CHWR Temp
lock_chwr_1
No
Off, On
TRUE
Evap Wat In Lock Value : (F)
CHWR Lock Value
chwr_lock_val_1
54.0
0
165
TRUE
Evap Wat Out Lock:
Lock EVAP LVG TMP
lock_chws_1
No
Off, On
TRUE
Evap Wat Out Lock Value: (F)
EVAP LVG TMP Lock Value
chws_lock_val_1
43.0
0
165
TRUE
Cond Wat In Lock :
Lock CWS Temp
lock_cws_1
No
Off, On
TRUE
Cond Wat In Lock Value : (F)
CWS Lock Value
cws_lock_val_1
85.0
0
165
TRUE
Cond Wat Out Lock:
Lock CWR Temp
lock_cwr_1
No
Off, On
TRUE
Cond Wat Out Lock Value: (F)
CWR Lock Value
cwr_lock_val_1
58.0
0
165
TRUE
Outdoor Air Lock:
Lock CHWS Temp
lock_oat_1
Yes
Off, On
TRUE
Outdoor Air Lock Value: (F)
OAT Lock Value
oat_lock_val_1
61.0
-20
140
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME
SCREW PID SEQUENCING DATA
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic PID Sequencing Data
VFD Minimum VDC Input: 4.3
VFD Minimum VDC Input
vfd_min_vdc_1
4.4
0
10
TRUE
VFD Minimum VDC In 3 Scr: 6.16
VFD Minimum for Three Screws vfd_min_vdc_three_scr_1
6.16
0
10
TRUE
VFD Minimum VDC In 4 Scr: 7.17
VFD Minimum for Four Screws
vfd_min_vdc_four_scr_1
7.17
0
10
TRUE
VFD Maximum VDC Input: 10.00
VFD Maximum VDC Input
vfd_max_vdc_1
10.0
0
10
TRUE
VFD Start PID for One Scr: 33
VFD Start PID for One Screw
vfd_start_pid_one_scr_1
33.0
0
500
TRUE
VFD Min PID for One Scr: 34
VFD Minimum PID for One
Screw
vfd_min_pid_one_scr_1
34.0
0
500
TRUE
VFD Max PID for One Scr: 75
VFD Maximum PID for One
Screw
vfd_max_pid_one_scr_1
75.0
0
500
TRUE
VFD Max One PID Min Two Scr: 85
VFD Max One PID Min Two
Screws
vfd_max_one_pid_min_two_scr_1
85.0
0
500
TRUE
VFD Min PID for Two Scr: 86
VFD Minimum PID for Two
Screws
vfd_min_pid_two_scr_1
86.0
0
500
TRUE
VFD Interim PID Two Scr: 123
VFDInterim PID for One Full One
Min Screws
vfd_interim_pid_two_scr_1
123.0
0
500
TRUE
VFD Max PID for Two Scr: 160
VFD Maximum PID for Two
Screws
vfd_max_pid_two_scr_1
160.0
0
500
TRUE
VFD Max Two PIDMinThree Scr:170
VFD Max Two PID Min Three
Screws
vfd_max_two_pid_min_three_scr_1
170.0
0
500
TRUE
VFD Min PID for Three Scr: 171
VFD Minimum PID for Three
Screws
vfd_min_pid_three_scr_1
171.0
0
500
TRUE
VFD IntPID One Full;Two Min:195
VFDInterim PID for One Full &
Two Min Screws
vfd_interim_pid_one_full_two_min_s
cr_1
195.0
0
500
TRUE
VFD IntPID Two Full;One Min:220
VFD Interim PID for Two Full &
One Min Screws
vfd_interim_pid_two_full_one_min_s
cr_1
220.0
0
500
TRUE
VFD Max PID for Three Scr: 245
VFD Maximum PID for Three
Screws
vfd_max_pid_three_scr_1
245.0
0
500
TRUE
VFD Max 3 PID Min Four Scr: 255
VFD Max Three PID Min Four
Screws
vfd_max_three_pid_min_four_scr_1
255.0
0
500
TRUE
VFD Min PID for Four Scr: 256
VFD Minimum PID for Four
Screws
vfd_min_pid_four_scr_1
256.0
0
500
TRUE
VFD IntPID One Full;3 Min: 274
VFDInterim PID for One Full &
Three Min Screws
vfd_interim_pid_one_full_three_min
_scr_1
274.0
0
500
TRUE
VFD IntPID Two Full;Two Min:292
VFD Interim PID for Two Half &
One Min Screws
vfd_interim_pid_two_full_two_min_s
cr_1
292.0
0
500
TRUE
VFD IntPID 3 Full; One Min: 311
VFD Interim PID for Three Full
One Min Screws
vfd_interim_pid_three_full_one_min
_scr_1
311.0
0
500
TRUE
VFD Max PID for Four Scr: 330
VFD Maximum PID for Four
Screws
vfd_max_pid_four_scr_1
330.0
0
500
TRUE
VFD Last PID: 340
VFD Last PID
vfd_last_pid_1
340.0
0
500
TRUE
Screw Runtime Before Flush 8.0h
Screw Runtime in Minutes
scr_runtime_before_flush_1
4.0
0
999
TRUE
Use Screw Flush Cycle
Use Screw Flush Cycle
use_scr_flush_1
Yes
No, Yes
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME
Page 10 of 15
10/9/2013
Product Line: UGW
Software Version: UGW-H.08B.13
Chiller Type: COOLING 4 PIPE
LOCAL ACCESS DISPLAY TABLE
MASTER MICRO FACTORY
SETUP FN8
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Master Ctrlr Fact Setup FN8
FN5
LINK(S): MODULE SIZE SELECTOR,PID COOL STG1 SETUP,PID HEAT STG1 SETUP,FIXED OPEN MODULE MENU,MOTORIZED VALVE OPTION,MOT VLV SIGNAL TO CLOSE MENU,
MASTER INPUT CHNLS 6, &10 SETUP,MASTER INPUT CHNL 7 DEM LIMIT SETUP,MASTER INPUT 8 & 11 SETUP,WATER MAINS & AIR TEMP LIMITS,STARTUP & STAGE DELAYS,
ALL MODULE COMP UNLOAD STATUS,AUTO HEAT TRG RESET ON OAT,COMPR SEQUENCING METHOD,HEAT BIN LOAD CAP% STATUS,COOL BIN LOAD CAP% STATUS,
MAIN TXV PID SETTINGS,MAIN TXV PSI PID SETTINGS,M1 & M2 MAIN TXV SETTINGS,M3 & M4 MAIN TXV SETTINGS,MODULE ALARM CONDITION RETRIES,
MODULE NUMBER MENU,KEYPAD,PREV, SYSTEM SETUP, HOME, ALARM
MODULE SIZE SELECTOR
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
Module Size Selector Screen Legend
Mod1 Size:
/ 1= Not Used/4=80Ton Mod
Module 1 Size
mod1_size_1
65 Ton
1
4
TRUE
Mod2 Size:
/NOTE:DO NOT SELECT 2 OR 3
Module 2 Size
mod2_size_1
65 Ton
1
4
TRUE
Mod3 Size:
Module 3 Size
mod3_size_1
65 Ton
1
4
TRUE
Mod4 Size:
Module 4 Size
mod4_size_1
65 Ton
1
4
TRUE
Mod5 Size:
Module 5 Size
mod5_size_1
Not Used
1
4
TRUE
Mod6 Size:
Module 6 Size
mod6_size_1
Not Used
1
4
TRUE
LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET
PID COOL STG1 SETUP
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Cool PID Stage #1 Setup
Stage One Cool PID Output : (%)
Stage 1 Cooling PID
stg1_clg_pid_1
106.719604
FALSE
Stage One Cool PID Interval:
Clg PID Interval
clg_interval_1
8.0 sec
1
100
TRUE
Stage One Cool PID P-Gain :
Clg PID P-gain
clg_p_gain_1
18.0
0
999
TRUE
Stage One Cool PID I-Gain#1:
Clg PID I-gain
clg_i_gain_1
0.35
0
99
TRUE
Max Cool Ramp Rate: - (F) (/min)
MAX COOL RAMP RATE
max_cool_ramp_rate_1
10.0 °F/min
1
20
TRUE
Clg PID Rise Fast: (%/min)
Clg PID Rise Fast
clg_rise_fast_1
12.0 sec
1
300
TRUE
Clg PID Rise Slow: (%/min)
Clg PID Rise Slow
clg_rise_slow_1
5.0 sec
1
300
TRUE
Clg PID Fall: (%/min)
Clg PID Fall
clg_fall_1
22.0
2
300
TRUE
Cool Deadbd1:
Clg PID DB1
clg_db1_1
0.3
0
99
TRUE
/CoolDeadbd2:
Clg PID DB2
clg_db2_1
0.0
0
99
TRUE
Stage One Cool PID I-Gain#2:
Clg PID IG2
clg_ig2_1
0.01
0
99
TRUE
PID Switching Differential: (%)
PID Differential Factor
pid_diff_fact_1
5.0
-100
100
TRUE
Cool Cntrl Setpt Offset: (F)
Cool Control Setpoint Offset
cl_cntrl_spt_offset_1
0.0
-250
250
TRUE
LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET
PID HEAT STG1 SETUP
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Heat PID Stage #1 Setup
Stage One Heat PID Output : (%)
Stage 1 Heating PID
stg1_htg_pid_1
0.0
FALSE
Stage One Heat PID Interval:
Htg PID Interval
htg_interval_1
2.0 sec
1
100
TRUE
Stage One Heat PID P-Gain :
Htg PID P-gain
htg_p_gain_1
20.0
0
999
TRUE
Stage One Heat PID I-Gain#1:
Htg PID I-gain
htg_i_gain_1
0.25
0
99
TRUE
Max Heat Ramp Rate: (F) (/min)
MAX HEAT RAMP RATE
max_heat_ramp_rate_1
10.0 °F/min
1
99
TRUE
Htg PID Rise Fast: (%/min)
Htg PID Rise Fast
htg_rise_fast_1
12.0 sec
1
300
TRUE
Htg PID Rise Slow: (%/min)
Htg PID Rise Slow
htg_rise_slow_1
4.0 sec
1
300
TRUE
Htg PID Fall: (%/min)
Htg PID Fall
htg_fall_1
25.0
2
300
TRUE
HeatDeadbd1:
Htg PID DB1
htg_db1_1
0.1
0
99
TRUE
/Heat Deadbd2:
Htg PID DB2
htg_db2_1
0.0
0
99
TRUE
Stage One Heat PID I-Gain#2:
Htg PID IG2
htg_ig2_1
0.0
0
99
TRUE
PID Switching Differential: (%)
PID Differential Factor
pid_diff_fact_1
5.0
-100
100
TRUE
Heat Cntrl Setpt Offset: (F)
Heat Control Setpoint Offset
ht_cntrl_spt_offset_1
1.0
-250
250
TRUE
LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET
FIXED OPEN MODULE MENU
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
FIX Mod Mot Vlv Open for Header Bypass
Open Ext Bypass if NO Comps ON?
Open Bypass Valves by NO
Comps ON
open_byp_vlv_on_no_cmps_1
Off
No, Yes
TRUE
Delay Before Closing Mot Valves:
Delay Before Closing Mot Vlv
close_vlv_delay_5
25.0
1
999
TRUE
Fix Module #1 as Open Module?:
Fix Mod1 as Open
fix_module1_open_1
Yes
No, Yes
TRUE
Never Close Module #1?:
Never Close Module #1
never_close_mod1_1
No
No, Yes
TRUE
Fix Module #2 as Open Module?:
Fix Mod2 as Open
fix_module2_open_1
No
No, Yes
TRUE
Never Close Module #2?:
Never Close Module #2
never_close_mod2_1
No
No, Yes
TRUE
Fix Module #3 as Open Module?:
Fix Mod3 as Open
fix_module3_open_1
No
No, Yes
TRUE
Never Close Module #3?:
Never Close Module #3
never_close_mod3_1
No
No, Yes
TRUE
Fix Module #4 as Open Module?:
Fix Mod4 as Open
fix_module4_open_1
No
No, Yes
TRUE
Never Close Module #4?:
Never Close Module #4
never_close_mod4_1
No
No, Yes
TRUE
Page 9 of 15
10/9/2013
Product Line: UGW
Software Version: UGW-H.08B.13
Chiller Type: COOLING 4 PIPE
LOCAL ACCESS DISPLAY TABLE
/C1SucPr: (ps)
Module 1 Comp 1 Suction
Pressure
m1_c1_suc_pres_stat_5
40.6
FALSE
C1DisTmpCal: (F)
M1C1 DIS Temp Calib. Point
m1c1_disch_temp_cp_5
0.0
-250
250
TRUE
/C1DisTp: (F)
Module 1 Comp 1 Disch Temp
m1_c1_disch_temp_stat_5
110.3
FALSE
C1SucTempCal: (F)
M1C1 SUC Temp Calib. Point
m1c1_suc_tmp_cp_5
0.0
-250
250
TRUE
/C1SucTp: (F)
Module 1 Comp 1 Suction Temp m1_c1_suct_temp_stat_5
53.6
FALSE
C1CompAmpCal:
M1C1 Amps Calib. Point
m1c1_amps_cp_5
3.0
-250
250
TRUE
/C1 Amps:
Module 1 Comp 1 Amps
m1c1_amps_stat_5
33.6
FALSE
LINK(S): PREV, SYSTEM SETUP, HOME
LOCK WATER TEMPS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value
Editable
Lock Main Header Water & Air Temps
Evap Wat In Lock :
Lock CHWR Temp
lock_chwr_1
No
Off, On
TRUE
Evap Wat In Lock Value : (F)
CHWR Lock Value
chwr_lock_val_1
54.0
0
165
TRUE
Evap Wat Out Lock:
Lock EVAP LVG TMP
lock_chws_1
No
Off, On
TRUE
Evap Wat Out Lock Value: (F)
EVAP LVG TMP Lock Value
chws_lock_val_1
43.0
0
165
TRUE
Cond Wat In Lock :
Lock CWS Temp
lock_cws_1
No
Off, On
TRUE
Cond Wat In Lock Value : (F)
CWS Lock Value
cws_lock_val_1
85.0
0
165
TRUE
Cond Wat Out Lock:
Lock CWR Temp
lock_cwr_1
No
Off, On
TRUE
Cond Wat Out Lock Value: (F)
CWR Lock Value
cwr_lock_val_1
58.0
0
165
TRUE
Outdoor Air Lock:
Lock CHWS Temp
lock_oat_1
Yes
Off, On
TRUE
Outdoor Air Lock Value: (F)
OAT Lock Value
oat_lock_val_1
61.0
-20
140
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME
SCREW PID SEQUENCING DATA
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic PID Sequencing Data
VFD Minimum VDC Input: 4.3
VFD Minimum VDC Input
vfd_min_vdc_1
4.4
0
10
TRUE
VFD Minimum VDC In 3 Scr: 6.16
VFD Minimum for Three Screws vfd_min_vdc_three_scr_1
6.16
0
10
TRUE
VFD Minimum VDC In 4 Scr: 7.17
VFD Minimum for Four Screws
vfd_min_vdc_four_scr_1
7.17
0
10
TRUE
VFD Maximum VDC Input: 10.00
VFD Maximum VDC Input
vfd_max_vdc_1
10.0
0
10
TRUE
VFD Start PID for One Scr: 33
VFD Start PID for One Screw
vfd_start_pid_one_scr_1
33.0
0
500
TRUE
VFD Min PID for One Scr: 34
VFD Minimum PID for One
Screw
vfd_min_pid_one_scr_1
34.0
0
500
TRUE
VFD Max PID for One Scr: 75
VFD Maximum PID for One
Screw
vfd_max_pid_one_scr_1
75.0
0
500
TRUE
VFD Max One PID Min Two Scr: 85
VFD Max One PID Min Two
Screws
vfd_max_one_pid_min_two_scr_1
85.0
0
500
TRUE
VFD Min PID for Two Scr: 86
VFD Minimum PID for Two
Screws
vfd_min_pid_two_scr_1
86.0
0
500
TRUE
VFD Interim PID Two Scr: 123
VFDInterim PID for One Full One
Min Screws
vfd_interim_pid_two_scr_1
123.0
0
500
TRUE
VFD Max PID for Two Scr: 160
VFD Maximum PID for Two
Screws
vfd_max_pid_two_scr_1
160.0
0
500
TRUE
VFD Max Two PIDMinThree Scr:170
VFD Max Two PID Min Three
Screws
vfd_max_two_pid_min_three_scr_1
170.0
0
500
TRUE
VFD Min PID for Three Scr: 171
VFD Minimum PID for Three
Screws
vfd_min_pid_three_scr_1
171.0
0
500
TRUE
VFD IntPID One Full;Two Min:195
VFDInterim PID for One Full &
Two Min Screws
vfd_interim_pid_one_full_two_min_s
cr_1
195.0
0
500
TRUE
VFD IntPID Two Full;One Min:220
VFD Interim PID for Two Full &
One Min Screws
vfd_interim_pid_two_full_one_min_s
cr_1
220.0
0
500
TRUE
VFD Max PID for Three Scr: 245
VFD Maximum PID for Three
Screws
vfd_max_pid_three_scr_1
245.0
0
500
TRUE
VFD Max 3 PID Min Four Scr: 255
VFD Max Three PID Min Four
Screws
vfd_max_three_pid_min_four_scr_1
255.0
0
500
TRUE
VFD Min PID for Four Scr: 256
VFD Minimum PID for Four
Screws
vfd_min_pid_four_scr_1
256.0
0
500
TRUE
VFD IntPID One Full;3 Min: 274
VFDInterim PID for One Full &
Three Min Screws
vfd_interim_pid_one_full_three_min
_scr_1
274.0
0
500
TRUE
VFD IntPID Two Full;Two Min:292
VFD Interim PID for Two Half &
One Min Screws
vfd_interim_pid_two_full_two_min_s
cr_1
292.0
0
500
TRUE
VFD IntPID 3 Full; One Min: 311
VFD Interim PID for Three Full
One Min Screws
vfd_interim_pid_three_full_one_min
_scr_1
311.0
0
500
TRUE
VFD Max PID for Four Scr: 330
VFD Maximum PID for Four
Screws
vfd_max_pid_four_scr_1
330.0
0
500
TRUE
VFD Last PID: 340
VFD Last PID
vfd_last_pid_1
340.0
0
500
TRUE
Screw Runtime Before Flush 8.0h
Screw Runtime in Minutes
scr_runtime_before_flush_1
4.0
0
999
TRUE
Use Screw Flush Cycle
Use Screw Flush Cycle
use_scr_flush_1
Yes
No, Yes
TRUE