Control Access Display Table
Page 7 of 15
10/9/2013
Product Line: UGW
Software Version: UGW-H.08B.13
Chiller Type: COOLING 4 PIPE
LOCAL ACCESS DISPLAY TABLE
Mod Active Status DisPr Alm SP:
Module Hi Disch Press Setpt
mod_hi_disch_press_sp_5
200.0
FALSE
Default Head Pressure Value:
Module Default Head Pressure
mod_default_hp_5
70.0
50
650
TRUE
Head Pressure Min Adj Value:
Module Head Pressure Positive
Adj
mod_hp_pos_adj_5
60.0
50
650
TRUE
SucPr Alm 134a
Low Suction Press Sp 134a
mod_lo_suc_press_sp_134_5
15.0
2
200
TRUE
SucPr Alm 410a
Low Suction Press Sp 410a
mod_lo_suc_press_sp_410_5
94.0
2
150
TRUE
/SucPr Alm 407C
Low Suction Press Sp 407C
mod_lo_suc_press_sp_407_5
50.0
2
120
TRUE
Mod Active Status SucPr Alm SP:
Module Low Suction Press Setpt mod_low_press_sp_5
15.0
FALSE
Mod SucPr Time Delay Before Alarm:
Module LO SUC PSI Delay
mod_lo_suc_psi_delay_5
30.0
0
999
TRUE
Mod Extra Low SucPr Alm SP:
Module LO-LO SUC PSI Setpoint mod_low_low_press_sp_5
0.0
-5
50
TRUE
Low Dis Pr Ctrl SP R134a
Low Head Press Sp 134a
mod_lo_disch_press_sp_134_5
100.0
20
350
TRUE
Low Dis Pr Ctrl SP R410a
Low Head Press Sp 410a
mod_lo_disch_press_sp_410_5
220.0
50
450
TRUE
Low Dis Pr Ctrl SP R407C
Low Head Press Sp 407
mod_lo_disch_press_sp_407_5
150.0
50
300
TRUE
Mod Active Status Low DisPr Alm SP:
Module Lo Disch Press Setpt
mod_lo_disch_press_sp_5
100.0
FALSE
M DisTp Alm SP
Module Hi Disch Temp
mod_hi_disch_tmp_5
225.0
100
325
TRUE
/M SucTp Alm SP
Module Low Suction Temp
mod_lo_suction_tmp_5
32.0
10
75
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME
LO SUC SPRHT & LO DISCH SPRHT SETPTS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Suc&Dis SuperHt Alrm Setpts
M Lo DisSuprHt
Module Low Disch SuperHt
Setpt
mod_lo_disc_supht_sp_5
15.0
TRUE
/M Lo SucSuprHt
Module Low Suct SuperHt Setpt mod_lo_suc_supht_sp_5
2.0
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME
FREEZE TARGET SETPOINT
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Freeze Target Setpts Menu
Freeze TrgSp (F)
Module Freeze Target Setpoint mod_freeze_trg_sp_5
36.0
0
50
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME
COMPR MIN MAX RUN TIMES
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
Compressor Min & Max Run Times
Compr Minimum Run Time (sec)
Module Compr Min Run Time
mod_cmpr_min_run_5
120.0
1
999
TRUE
Compr Minimum Off Time (sec)
Module Compr Min Off Delay
mod_cmpr_off_delay_5
150.0
1
999
TRUE
LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET
COMPR ALARM DELAY
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Compr Alarm Delays
Mod Alm Delay
Module Compr Status Alarm
Delay
mod_comp_stat_alm_delay_5
9999.0
5
999
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
MODULE WATER TEMP LIMITS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Module Water Out Temp Limits
Mod Evap Wat Out Lo Limit: (F)
Module Freeze Target Setpoint mod_freeze_trg_sp_5
36.0
0
165
TRUE
Mod Evap Wat Out Hi Limit: (F)
Module High Evaporator Leaving
Temp at Startup
mod_high_evap_lvg_tmp_5
90.0
0
165
TRUE
Mod Cond Wat Out Lo Limit: (F)
Module Low Condenser Leaving
Temp. Setpoint
mod_low_cond_lvg_sp_5
50.0
0
165
TRUE
Mod Cond Wat Out Hi Limit:
HI WTR OUT UGW
UCW Module High Cond Leaving
Temp at Startup
ugw_mod_cwr_trg_sp_5
118.0
10
165
TRUE
/HI WTR OUT UGH
UCH Module High Cond Leaving
Temp at Startup
ugh_mod_cwr_trg_sp_5
140.0
10
165
TRUE
Mod Cond Wat Out Hi Limit: (F)
Module Leaving Cond Water
Temp Setpoint
mod_cwr_trg_sp_5
118.0
10
165
FALSE
LINK(S): PREV, SYSTEM SETUP, HOME
SCREW COMP ALARM SETPOINTS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
Screw Comp Alarm Setpoints
Screw Comp Max Amps Allowed 460:
Compressor Max Amps
mod_max_amps_sp_5
105.0
1
999
TRUE
Winding Temp Correlation to ohms:
Compr Max Winding Temp
Sensor Resis
mod_max_wind_sens_ohms_5
275.0
1
999
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
SERVICE MENU SETUP FN7
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
Page 7 of 15
10/9/2013
Product Line: UGW
Software Version: UGW-H.08B.13
Chiller Type: COOLING 4 PIPE
LOCAL ACCESS DISPLAY TABLE
Mod Active Status DisPr Alm SP:
Module Hi Disch Press Setpt
mod_hi_disch_press_sp_5
200.0
FALSE
Default Head Pressure Value:
Module Default Head Pressure
mod_default_hp_5
70.0
50
650
TRUE
Head Pressure Min Adj Value:
Module Head Pressure Positive
Adj
mod_hp_pos_adj_5
60.0
50
650
TRUE
SucPr Alm 134a
Low Suction Press Sp 134a
mod_lo_suc_press_sp_134_5
15.0
2
200
TRUE
SucPr Alm 410a
Low Suction Press Sp 410a
mod_lo_suc_press_sp_410_5
94.0
2
150
TRUE
/SucPr Alm 407C
Low Suction Press Sp 407C
mod_lo_suc_press_sp_407_5
50.0
2
120
TRUE
Mod Active Status SucPr Alm SP:
Module Low Suction Press Setpt mod_low_press_sp_5
15.0
FALSE
Mod SucPr Time Delay Before Alarm:
Module LO SUC PSI Delay
mod_lo_suc_psi_delay_5
30.0
0
999
TRUE
Mod Extra Low SucPr Alm SP:
Module LO-LO SUC PSI Setpoint mod_low_low_press_sp_5
0.0
-5
50
TRUE
Low Dis Pr Ctrl SP R134a
Low Head Press Sp 134a
mod_lo_disch_press_sp_134_5
100.0
20
350
TRUE
Low Dis Pr Ctrl SP R410a
Low Head Press Sp 410a
mod_lo_disch_press_sp_410_5
220.0
50
450
TRUE
Low Dis Pr Ctrl SP R407C
Low Head Press Sp 407
mod_lo_disch_press_sp_407_5
150.0
50
300
TRUE
Mod Active Status Low DisPr Alm SP:
Module Lo Disch Press Setpt
mod_lo_disch_press_sp_5
100.0
FALSE
M DisTp Alm SP
Module Hi Disch Temp
mod_hi_disch_tmp_5
225.0
100
325
TRUE
/M SucTp Alm SP
Module Low Suction Temp
mod_lo_suction_tmp_5
32.0
10
75
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME
LO SUC SPRHT & LO DISCH SPRHT SETPTS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Suc&Dis SuperHt Alrm Setpts
M Lo DisSuprHt
Module Low Disch SuperHt
Setpt
mod_lo_disc_supht_sp_5
15.0
TRUE
/M Lo SucSuprHt
Module Low Suct SuperHt Setpt mod_lo_suc_supht_sp_5
2.0
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME
FREEZE TARGET SETPOINT
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Freeze Target Setpts Menu
Freeze TrgSp (F)
Module Freeze Target Setpoint mod_freeze_trg_sp_5
36.0
0
50
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME
COMPR MIN MAX RUN TIMES
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
Compressor Min & Max Run Times
Compr Minimum Run Time (sec)
Module Compr Min Run Time
mod_cmpr_min_run_5
120.0
1
999
TRUE
Compr Minimum Off Time (sec)
Module Compr Min Off Delay
mod_cmpr_off_delay_5
150.0
1
999
TRUE
LINK(S): PREV, ALARM, SYSTEM SETUP, CLOCKSET
COMPR ALARM DELAY
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Compr Alarm Delays
Mod Alm Delay
Module Compr Status Alarm
Delay
mod_comp_stat_alm_delay_5
9999.0
5
999
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
MODULE WATER TEMP LIMITS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic Module Water Out Temp Limits
Mod Evap Wat Out Lo Limit: (F)
Module Freeze Target Setpoint mod_freeze_trg_sp_5
36.0
0
165
TRUE
Mod Evap Wat Out Hi Limit: (F)
Module High Evaporator Leaving
Temp at Startup
mod_high_evap_lvg_tmp_5
90.0
0
165
TRUE
Mod Cond Wat Out Lo Limit: (F)
Module Low Condenser Leaving
Temp. Setpoint
mod_low_cond_lvg_sp_5
50.0
0
165
TRUE
Mod Cond Wat Out Hi Limit:
HI WTR OUT UGW
UCW Module High Cond Leaving
Temp at Startup
ugw_mod_cwr_trg_sp_5
118.0
10
165
TRUE
/HI WTR OUT UGH
UCH Module High Cond Leaving
Temp at Startup
ugh_mod_cwr_trg_sp_5
140.0
10
165
TRUE
Mod Cond Wat Out Hi Limit: (F)
Module Leaving Cond Water
Temp Setpoint
mod_cwr_trg_sp_5
118.0
10
165
FALSE
LINK(S): PREV, SYSTEM SETUP, HOME
SCREW COMP ALARM SETPOINTS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
Screw Comp Alarm Setpoints
Screw Comp Max Amps Allowed 460:
Compressor Max Amps
mod_max_amps_sp_5
105.0
1
999
TRUE
Winding Temp Correlation to ohms:
Compr Max Winding Temp
Sensor Resis
mod_max_wind_sens_ohms_5
275.0
1
999
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
SERVICE MENU SETUP FN7
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
Page 8 of 15
10/9/2013
Product Line: UGW
Software Version: UGW-H.08B.13
Chiller Type: COOLING 4 PIPE
LOCAL ACCESS DISPLAY TABLE
CoolLogic Service Menu Setup FN7
LINK(S): DIAGNOSTICS MANUAL MODE,CALIB WATER DIFF PRESS SENSORS,CALIB WATER MAINS & AIR TEMPS,ALL MODULE SENSOR CALIBRATION MENUS,
ALL MODULE COMP UNLOAD STATUS,RESET MODULE SENSOR OOR ALARMS,RESET COMP ALARMS,MODULE WATER TEMP LIMITS,WATER MAINS & AIR TEMP LIMITS,
PUMP DOWN SETUP,LOCK WATER TEMPS,RESET COMP RUNTIME & CYCLES,TIME MSTR,SCREW PID SEQUENCING DATA,PREV, SYSTEM SETUP, HOME, ALARM
DIAGNOSTICS MANUAL MODE
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
(/)
Link (/)
Manual Mode M1, Manual Mode M2
Link (/)
Manual Mode M3, Manual Mode M4
/
SWAP LEAD COMPR:
Manually Refresh Lead Module man_refr_modlead_1
Do Not
Refresh Lead
Do Not Refresh
Lead, Refresh
Lead
TRUE
LINK(S): MANUAL MODE M5, MANUAL MODE M6,LOCK WATER TEMPS,PREV, SYSTEM SETUP, HOME, ALARM
MANUAL MODE Mx
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value
Editable
M1 Manual Mode
M1 Manual Mode Enable
m1_man_mode_5
Off
Off, On
TRUE
M1C1 Manual ON
M1C1 Manual Run
m1c1_man_run_5
Off
Off, On
TRUE
M1C1 Status:
Module 1 Comp 1 Status
m1_comp1_status_5
On
Off, On
FALSE
LINK(S): PREV, SERVICE MENU SETUP, HOME
CALIB WATER DIFF PRESS SENSORS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
Calibrate Water Diff Press Sensors
Cool Water Dif Psi Stat: (PSID)
Diff Press Cool Load
diff_press_cool_load_1
8.48872 °F
FALSE
Cool PsiCalib Offset: (PSID)
Chilled Diff Press Calibration
Point
chwpsi_cali_point_1
0.0
-199
199
TRUE
Heat Water Dif Psi Stat: (PSID)
Diff Press Heat Load
diff_press_heat_load_1
8.053761 °F
FALSE
Heat Psi Calib Offset: (PSID)
Cond Diff Press Calibration Point cwpsi_cali_point_1
0.0
-199
199
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME, ALARM
CALIB WATER MAINS & AIR TEMPS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
Calibrate Main Header Water &Air Temps
Evap InSens: (F)
EVAP IN TMP
chwr_temp_1
54.4 °F
FALSE
/Evap Wat In: (F)
CHWR In Temp Status
chwr_stat_1
54.4
FALSE
Evap In Calib Offset: (F)
CHWR Temp Calibration Point
chwr_cali_point_1
0.0
-250
250
TRUE
Evp OutSens: (F)
EVAP OUT TMP
chws_temp_1
50.1 °F
FALSE
/Evap WatOut: (F)
CHWS Out Temp Status
chws_stat_1
50.2
FALSE
Evap Out Calib Offset: (F)
CHWS Temp Calibration Point
chws_cali_point_1
0.0
-250
250
TRUE
Cnd Out Sens: (F)
COND OUT TMP
cwr_temp_1
83.3 °F
FALSE
/CndWat Out: (F)
CWR Out Status
cwr_stat_1
83.3
FALSE
Cond Out Calib Offset: (F)
CWR Calibration Point
cwr_cali_point_1
0.0
-250
250
TRUE
Cond In Sens: (F)
COND IN TMP
cws_temp_1
67.3 °F
FALSE
/Cnd Wat In: (F)
CWS In Temp Status
cws_stat_1
67.3 °F
FALSE
Cond In Calib Offset: (F)
CWS Temp Calibration Point
cws_cali_point_1
0.0
-250
250
TRUE
Outdoor Sens: (F)
OA Temp
oat_1
-60.2 °F
FALSE
/Outdr Air : (F)
OAT Status
oat_stat_1
61.0
FALSE
Outdoor Air Calib Offset: (F)
OAT Calibration Point
oat_cali_point_1
0.0
-250
250
TRUE
LINK(S): PREV, SYSTEM SETUP, HOME
ALL MODULE SENSOR CALIBRATION MENUS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
CoolLogic All Module Calibration Menus
LINK(S): MODULE 1 SENSOR CALIBRATIONS,MODULE 2 SENSOR CALIBRATIONS,MODULE 3 SENSOR CALIBRATIONS,MODULE 4 SENSOR CALIBRATIONS,
MODULE 5 SENSOR CALIBRATIONS,MODULE 6 SENSOR CALIBRATIONS,PREV, SYSTEM SETUP, HOME, ALARM
MODULE X SENSOR CALIBRATIONS
Screen Display
Content
BACnet Object
Default
Min. Value
Max. Value Editable
ClimaCool Module 1 Water Calibrations
EvpOutCalib: (F)
M1 CHWS Temp Calib. Point
m1_chws_temp_cp_5
0.0
-250
250
TRUE
/EvpOutSta: (F)
M1 Evap Leaving Temp
m1_chws_temp_stat_5
51.7
FALSE
CndOutCal: (F)
M1 CWR Temp Calib. Point
m1_cwr_temp_cp_5
0.0
-250
250
TRUE
/CondOutStat: (F)
M1 Cond Leaving Temp
m1_cwr_temp_stat_5
84.6
FALSE
ClimaCool Module 1 Refrig Calibrations
C1DisPresCal: (psi)
M1C1 DIS Pressure Calib. Point
m1c1_disch_pres_cp_5
0.0
-250
250
TRUE
/C1DisPr: (psi)
Module 1 Comp 1 Disch Press
m1_c1_disch_pres_stat_5
99.3
0
350
FALSE
C1SucPresCal: (psi)
M1C1 SUC Pressure Calib. Point m1c1_suc_pres_cp_5
0.0
-250
250
TRUE