016-030-B0-005, Rev. C

Table 2-2, APX Output Voltage Reconfi guration

The APX 90V series has a user-selectable output voltage between 60VAC, 75VAC, and
90VAC. Verify appropriate output voltage selection for each application. The default setting is
90VAC.

To reconfi gure the output voltage, move the 12-gauge black wire to the appropriate output
tap on the transformer. See Table 2-2.

NOTE:

If the SIL-C option is installed, the 20-gauge black wire connected to the SIL-C must remain connected
to the 60VAC (tap 6A) output tap.

Black Wire

White Wire

90VAC / 6C

5

75VAC / 6B

5

60VAC / 6A