6 Maintenance

The equipment requires regular maintenance. The maintenance should be done by qualified service personnel
only.

WARNING: HIGH VOLTAGE AND SHOCK HAZARD.

Use extreme care when working inside the enclosure/shelf while the system is energized. Do not make
contact with live components or parts. Static electricity may damage circuit boards, including RAM chips.
Always wear a grounded wrist strap when handling or installing circuit boards.

6.1

General maintenance schedule

Description

Interval

Clean ventilation openings

1-6 months

Inspect all cable connections, re-torque if necessary

1 year

Verify alarm/control settings

1 year

Verify alarm relay operation

1 year

Clean HVAC filter

2-6 months

6.2

Air conditioner

6.2.1 Air conditioner settings

The air conditioner is pre-programmed with default settings at the factory. Refer to the air conditioner manual if
you need to adjust these settings.

6.2.2 Air conditioner filter

Air conditioners often fail due to lack of maintenance, specifically dirty filters. Implement a structured filter
inspection/maintenance schedule to avoid unnecessary air conditioner failures.

6.2.3 High temperature alarms and air conditioner failures

The air conditioner is not always thoroughly tested at the factory. If the air conditioner fails to switch on when it
should, refer to the air conditioner manual and check the temperature settings.

If the air conditioner appears to be working properly but the

“Hi-Temp” alarm is on, check that the enclosure's Hi-

Temp alarm thermostat is correctly set.