Relay 2 output group (alarm assignment) 15, Test relay 2 15, 15 relay menu (c – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, 508 & 750) Setup Programming Guide User Manual
Page 90: Relay 2 output group (alarm assignment)

Relays Setup
Page
15 - 3
15
Relay Menu (C
ONTINUED
...
FROM
PREVIOUS
PAGE
)
RELAY 2
Go back to RELAYS menu and push
M2
under
TIMEOUT
RELAY 2 to access this menu.
RELAY TIMEOUT 2
15
0 to 3600
(Input an automatic relay time-out / switch-off value in
seconds... 0 = no time-out, the attendant must press
ACK
to switch the relay off, 3600 = 60 minutes or 1 hour
time-out )... Input a considerable automatic relay time-
out value –
especially when the relay controls an
external alarm device.
Relay 2 Output
Group (alarm assignment)
Select / assign output group(s) to activate RELAY 1 on alarm / limit.
OUT GRPS
RELAY OUTPUT GROUPS 1
GROUP
– – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – –
A
1
32
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z AA BB CC DD EE FF
Fill–in RELAY 2 Output – Group Assignments Below:
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
A A
B B
C C
D D
E E
F F
TEST Relay 2
Press
M3
key.
TESTING...
RELAY switches on and off...
listen for clicking sound.
HIT ANY KEY TO QUIT
Press any key to stop the test or wait for the time-out to
switch the relay off