Tanks - special tank n menu 2, Tanks – tank alarm n menu – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, 508 & 750) Setup Programming Guide User Manual
Page 28

Tank Setup
Page
2 - 5
2
Tanks – TANK ALARM N Menu
(C
ONTINUED
...
FROM
PREVIOUS
PAGE
)
LL LIM OG N
(assign Alarm Limits to Output Group)
L L PRODUCT OUTPUT GROUP N
(32 OGs available... see Worksheet #2 or #3)
NONE
Not assigned to an output Group (OG)
GROUP A-FF
One OG selected (
A = 1
ST
OG, FF = 32
ND OG
)
ALL GROUPS
All OGs selected
Use
UP/DOWN
▲ ▼
keys to choose an OG.
Press
ENTER
to accept this data.
WATER LIM N
HIGH WATER LEVEL LIMIT N
+4.0000
0.0 to 9999.0 (enter alarm limit)
Press
ENTER
to accept this data.
W LIM OG N
(assign Alarm Limits to Output Group)
HIGH WATER OUTPUT GROUP N
(32 OGs available... see Worksheet #2 or #3)
NONE
Not assigned to an output Group (OG)
GROUP A-FF
One OG selected (
A = 1
ST
OG, FF = 32
ND OG
)
ALL GROUPS
All OGs selected
Use
UP/DOWN
▲ ▼
keys to choose an OG.
Press
ENTER
to accept this data.
WATER LIM N and W LIM OG N are not available for PRESSURE probes, since they do
not measure water level.
Tanks – SPECIAL TANK N Menu
•
If
STANDARD tanks are selcted, then these menu options will not be available.
•
Correction Tables:
If the Special Tank is not a perfect cylinder or has a domed end,
then you must program a correction table (100 correction points can be programmed).
Two values are required per point / position (POS #). These are level and volume, which
are found in the manufacturers’ tank table /chart, input these accurately. Always input 0
level and 0 volume for the first point, and max. level and max. volume for the last point.
The number of points in between determines the accuracy of the strapping table.
•
Cylindrical Tanks:
Select diameter and input the internal tank diameter value, and
set the length to the internal length of the tank (correction tables are usually not needed
with cylindrical tanks).
•
Vertical or Rectangular tanks: Select diameter and input the internal tank diameter or
depth, and set its
length to zero ( 0 ). Input 0 level and 0 volume for the first point, and
max. level and max. volume for the last point.
•
Correction Points are automatically sorted from lowest to highest level. The lowest
level is closest to the bottom of the tank.
SPECIAL
SPECIAL TANKS
SPECIAL 1
SPECIAL 2
:
Use
UP/DOWN
▲▼
keys to display tanks 5-8.
SPECIAL 8
NOTE
☞
NOTE
☞