Cpm menu (continued ... from previous page) – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, 508 & 750) Setup Programming Guide User Manual
Page 110

19
Page
19 - 2
Tank Sentinel Setup Programming Guide
CPM Menu (Continued ... FROM PREVIOUS PAGE)
CATHODIC PROTECTION
DATA
Press
M1
key.
CATHODIC PROTECTION DATA
ENABLE
Press
M1
key.
CPM ENABLE
Use
UP/DOWN
▲
▼
keys to show choices.
NO
(select
YES if a TS-CPM unit is installed)
YES
Press
ENTER
to accept this data.
ADDRESS
Press
M2
key.
CPM SENSOR ADDRESS
(accessing this menu is not required for SETUP)
112
Keep the default value (112)
CONFIG
Press
M3
key.
CPM SENSOR SETUP
(accessing this menu is not required for SETUP)
CHECKING ADDRESS ...
(the system is searching for the current address)
— Press the
CANCEL key to display the CATHODIC PROTECTION Menu —
ALARM
Press
M2
key.
CATHODIC PROTECTION ALARM
AMPS
Press
M1
key.
CPM CURRENT LIMIT
+10.0000
0.0 to 10 amps
Use keypad to input a current limit number.
Press
ENTER
to accept this data.
AMPS OG
Press
M2
key.
CPM CURRENT LIMIT OUTPUT GROUP
(32 OGs available ... see Worksheet #19-1)
NONE
Not assigned to an Output Group (OG)
GROUP A-FF
One OG selected (A=1st OG, FF=32nd OG)
ALL GROUPS
All OGs selected
Use
UP/DOWN
▲
▼
keys to choose an OG.
Press
ENTER
to accept this data.
— Press the
CANCEL key two times to display the SETUP Menu —
(input 80% of the output amperage
level that was documented on the
last UST Survey Report)