Scald (tank leak) test menu 11, Scald (tank leak) test menu – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, 508 & 750) Setup Programming Guide User Manual
Page 75

11
Page
11- 2
Tank Sentinel Setup Programming Guide
SCALD (tank leak) Test Menu
N = Tanks 1 – 8
(only the NO. of TANKS
SCALD TESTS
programmed in the System menu will appear)
CONFIDNCE
SCALD CONFIDENCE
99.0%
Keep the default 99.0% value
90.0%
95.0%
97.5%
Press
ENTER
to accept this data.
PRECISION
SCALD TEST PRECISION
+0.2
Keep the default 0.2 gph monthly test value
Press
ENTER
to accept this data.
INTERVAL
SCALD INTERVAL
18
Keep the default value (18)
Press
ENTER
to accept this data.
QUALIFY
(minimum volume percent before starting a test)
SCALD VOLUME QUALIFY
+0
0.0 to 99.0%
Use keypad to input a percentage.
Press
ENTER
to accept this data.
Reference Local codes (and/or State / Province /
Federal codes) for the minimum percentage of
tank-volume-capacity before a leak test results
can, or will, be considered acceptable. Input the
minimum-acceptable volume based on these
regulations.
ENABLE
(select tanks to be SCALD leak tested)
SCALD ENABLE
Keep the default – all tanks ENABLED
TANK 1
TANK 2
Use
UP/DOWN
▲
▼
keys to show more choices.
:
TANK 8
Press the (
M
) key to select a TANK #.
SCALD ENABLE
ENABLED
Use
UP/DOWN
▲
▼
keys to change the setting.
DISABLED
Press
ENTER
to accept this data.
Press the
CANCEL
key to return to the SCALD TESTS menus.
— C
ONTINUED
ON
NEXT
PAGE
—
Monthly
Compliance
Yearly Test
SCALD Leak Test:
0.2 gph
0.1 gph
Precision:
Threshold = 1/2 of Leak Test value
NOTE
☞